D500
| CI/EDP300-EN Rev. A 31
8.3
Equipment in type of protection "n" or device dust
ignition protection through housing "tb"
ZELM 11 ATEX 0456 X (EC type examination certificate)
II 3G Ex nA IIC T6 or T4 Gc
II 2D Ex tb IIIC T55°C or T100°C Db
Ta = -40 ° … 40 ° or 80
IECEx ZLM 11.0001 X
Ex nA IIC T6 or T4 Gc
Ex tb IIIC T55 °C or T100°C Db
Ta = -40 ° … 40 ° or 80
Temperature
class
Ambient temperature
Surface temperature
T4
-40 … 80 °C (-40 … 176 °F)
100 °C (212 °F)
T6
-40 … 40 °C (-40 … 104 °F)
55° C (131 °F)
8.4
Electrical connections non-sparking ATEX/IECEx
Equipment in type of protection "n" or device dust ignition
protection through housing "tb"
Signal circuit (AI) (ter11 -12):
I
N
≤ 22 mA
U
max
≤ 30 V
Switching input (DI) (ter81 -82):
U
N
≤ 30 V
Switching output (DO) (ter83 -84):
U
N
≤ 30 V
Shutdown module (ter41 -42):
U
N
≤ 30 V
Analog feedback module (UAI) (ter31 -32)
I
N
≤ 22 mA
U
N
≤ 30 V
Universal analog input module (ter21 -22)
I
N
≤ 22 mA
U
max
≤ 30 V
Digital feedback module
(terminals: SW 1: +41 -42, SW 2: +51 -52)
Per output:
U
N
≤ 30 V
Digital output module (proximity switches)
(terminals limit 1: +51 -52, limit 2: +41 -42)
Per output:
I
N
≤ 25 mA
U
N
≤ 16 V
When using proximity switch SJ2_S1N (NO), the positioner
may only be used at an ambient temperature range of
-25 ... 80 °C (-13 ... 176 °F).
Change from two to one column