background image

24

V D 4 X  

I N S T R U C T I O N   M A N U A L

Maintenance

Maintenance serves to ensure trouble-free 
operation and achieve the longest possible 
working life of the switchgear. In accordance 

with DIN 31051, IEC 62271-1 it comprises the

following closely related activities:

Inspection:

 Determination of the actual 

condition

Servicing:

 Preservation of a functional 

condition

Repair:

 Measures to restore the functional 

condition

5.1 5.1 General

Vacuum circuit-breakers are characterized by 
their simple and robust construction. They have 
a long life expectancy. Their operating mechanisms 
have a low maintenance requirement, and the 
interrupters are maintenance-free during their 
working life. There is no adverse effect on the 
vacuum, even from frequent switching of operating 
and short-circuit currents.

The servicing intervals and scope are determined 
by environmental influences, the switching 
sequences and number of short-circuit breaking 
operations.

Note

The following must be observed for all 
maintenance work:

•  The relevant specifications in section 

“Standards and specifications”

•  Notes on safety at work in section 

“Commissioning / Operation”

•  Standards and specifications in the country 

of installation

Maintenance work may only be performed by fully 
trained personnel, observing all the relevant 
safety regulations. It is recommended that ABB 
after-sales service personnel should be called 
in, at least during the performance of servicing 
and repair work.

While the work is in progress, all supply voltage 

sources must also be disconnected and secured 
to prevent reconnection.

Note

In order to prevent accidents 
(particularly injury to hands!) extreme 
care should be taken during all repair 
work on the operating mechanism, 
especially with front plate removed.

The spiral spring in the spring energy 
storage mechanism, for instance, 
retains a basic tension which is 
independent of the charging and 
discharging processes during 
switching, so as to ensure correct 
function. This spring energy can be 
inadvertently released if work is 
performed incorrectly on the spring 
mechanism!

5.1.1 Service-life

Typical life-expectancies for VD4X circuit-breakers.

Vacuum interrupter

Up to 30,000 switching cycles (see section 
“Permissible numbers of switching cycles” page 9)

Device

Up to 30,000 operating cycles, depending on 

switch type and assuming conscientiously 
performed inspection and maintenance work 
and normal operating conditions.

5.2 Inspection and functional testing

5.2.1 Switching devices in general

•  The proper condition of the switching device 

is to be verified by regular inspection

•  Inspection at fixed intervals may be waived if 

the switchgear is permanently monitored by a 
qualified personnel

•  The checks first and foremost comprise visual 

examination for contamination, corrosion and 
moisture

•  In unusual operating conditions (including 

adverse climatic conditions) and/or special 
environmental pollutions (e.g. heavy 
contamination and aggressive atmosphere), 
inspection may also be necessary at shorter 
intervals

•  If an incorrect condition is found, appropriate 

servicing measures are to be initiated

5.2.2 Stored-energy spring mechanism

Functional testing of the operating mechanism 
is to be performed:

•  after 5,000 operating cycles or
•  during servicing work as set out in section 

“Inspection, switching devices in general”

Prior to functional testing, switch the breaker 
off and isolate the outgoing feeder.

Note

Isolate and secure the working area in accordance 
with the safety regulations specified by DIN 
VDE/IEC.

Scope of functional testing

•  Perform several switching operations under 

no-load, above all with circuit-breakers seldom 
operated in normal service

•  Switch off the charging motor (if fitted) and 

discharge the spring energy storage  
mechanism by ON/OFF switching operations

•  

Examine visual the condition of the lubrication 

on rotary bearings, sliding surfaces, etc

•  

Check the proper mechanical/electrical sequence 

of the individual functions

5.2.3 Breaker pole

No inspection of the breaker pole above and 
beyond the stipulations of section “Inspection, 
switching devices in general” is necessary.

5.3 Servicing

5.3.1 Switching devices in general

All parts which are located within the gas 
compartment and are therefore inaccessible 
require no maintenance.

5.3.2 Stored-energy spring mechanism

Servicing of the operating mechanism is to be 
performed after 10,000 operating cycles.

Prior to servicing, open the circuit-breaker, 
isolate and secure the outgoing feeder to 
prevent reconnection.

Scope of servicing

•  Switch off the charging motor and release the 

spring energy storage mechanism by closing 
and opening the breaker

•  As a precaution, replace parts subject to high 

climatic and mechanical stresses

•  For replacement of highly stressed 

parts, release the pretension of the 
spiral spring, noting the 
pretensioning dimension. Take care 
when handling springs

• Relubricate pawls, support shafts, 

sliding and rotating bearing surfaces. 

Lubricant: Isoflex Topas NB 52

•  Check the fit of fasteners (e.g. locking 

pins) in cranks, pins, bolts etc. Check 
the tightness of fastening bolts

•  Always replace any spring lock 

washers, split pins and other 
fasteners removed during the work 
with new parts when reassembling 
the equipment

•  Check the general condition of the 

operating mechanism and recharge 
the spring to the pre-tensioning 
dimension noted

•  Perform comprehensive mechanical 

and electrical functional tests 
(Observe the setting instructions)

Note

Above mentioned work may only be performed 
by servicing personnel from ABB or adequately 
trained specialist staff.

5.3.3 Breaker pole

The breaker pole with the vacuum interrupter is 
maintenance-free up to the permissible number 
of operating cycles as sent down in section 
“Permissible number of vacuum interrupter 
switching operations”:

•  When the permissible number of operating 

cycles as a function of the breaking current has 
been reached, the vacuum interrupters are to 

be replaced (see section 2.3)

Note

The above activities may only be performed by 
servicing personnel from ABB or adequately 
trained specialist staff, as they require work on 
the circuit-breaker itself.

5.4 Repair

5.4.1 Run-on block

Should irregularities occur in the area of the 
internal control mechanism and the charging 
function of the spring energy storage mechanism, 
a run-on block blocks the next closing operation 
in sequence.

This is a protective function to prevent damage 
to the circuit-breaker.

Release of the run-on block may only be performed 
by servicing personnel from ABB or adequately 
trained specialist stuff.

5.4.2 Replacement of circuit-breaker parts and 

ac cessories

•  Only remove and reassemble circuit-breaker 

parts and accessories when the breaker has 
been switched off and the working area 
properly isolated and secured to prevent 
reconnection. The spring energy storage 
mechanism must be discharged

•  All supply voltage sources must be 

disconnected and secured to prevent 
reconnection during the removal and 
installation work

•  Connecting and adjusting elements 18 and 18.1

 

to 18.4 (see Figure 3/1) must be removed, inter

 

alia, prior to removal of the circuit-breaker 
operating mechanism

•  

Only use original parts when replacing defective 

components

Summary of Contents for VD4X

Page 1: ... VD4X Vacuum circuit breaker INSTRUCTION MANUAL VD4X Vacuum circuit breaker ...

Page 2: ......

Page 3: ...28 Summary Technical data Structure and mode of action Commissioning Operation Maintenance Application of the X ray regulations Comparison of designations to IEC 81346 1 IEC 81346 2 IEC 61346 1 IEC 61346 2 and VDE DIN 40719 Part 2 Content ...

Page 4: ...rning symbol Ensure that the technical data in the specifica tion are not exceeded during operation of the switching device or switchgear The instruction manual must be kept accessible to all persons entrusted with work on the switching device It is to be ensured that the number of the instruction manual used is iden tical with the number on the type plate of the circuit breaker The user s personn...

Page 5: ...er installations with rated voltages above 1 kV Accident prevention regulations issued by the appropriate professional bodies or comparable organizations Safety guidelines for auxiliary and operating materials Order related details provided by the switchgear manufacturer 1 3 Operating conditions 1 3 1 Normal operating conditions Design to IEC 62271 1 High voltage switchgear and controlgear Part 1 ...

Page 6: ...1 2425 31 3612 31 3625 31 3625 40 4012 31 4025 31 4025 40 Rated Voltage kV 12 12 17 5 24 24 36 36 36 40 5 40 5 40 5 Rated current A 1250 1600 2500 1250 1250 1600 2500 1250 2500 1250 2500 1250 2500 2500 Rated short circuit breaking current symm 8 kA 31 5 31 5 31 5 31 5 31 5 31 5 31 5 40 31 5 31 5 40 Rated short circuit making current peak 8 kA 80 80 80 80 80 80 80 100 80 80 100 Rated short circuit ...

Page 7: ...70 ms 30 45 ms 27 45 ms 2 15 ms 60 ms 20 ms 120 ms 1 20 ms 80 ms 1 2 2 Technical data Equipment 2 2 1 Charging motor for stored energy spring mechanism Supply voltage V AC V DC Motor protection ABB Stotz Automat A 1 60 S 281 UC K 1 60 0 75 0 75 6 00 S 282 UC K 6 00 4 00 3 00 1 60 1 60 0 75 0 75 Power consumption approx 260 VA 3 approx 200 260 W 3 Charging time maximum 2 s 15 15 15 15 15 15 15 15 1...

Page 8: ...X pole side Figure 2 1c Vacuum circuit breaker type VD4X mechanism side with front plate Figure 2 1d Vacuum circuit breaker type VD4X pole side Figure 2 1e Vacuum circuit breaker type VD4X mechanism side with front plate Figure 2 1f Vacuum circuit breaker type VD4X pole side Figure 2 1a Figure 2 1b Figure 2 1c Figure 2 1d Figure 2 1e Figure 2 1f ...

Page 9: ... 3 4 5 6 7 8 10 5 2 3 4 5 6 7 8 10 9 20 30 40 50 10 0 05 5 0 1 0 2 0 3 0 4 0 5 0 6 0 8 1 6 7 8 10 2 3 4 5 6 7 8 10 2 2 3 4 5 6 7 8 10 3 2 3 4 5 6 7 8 4 2 3 4 5 6 7 8 10 5 2 3 4 5 6 7 8 10 9 20 30 40 50 10 Number of operating cycles n Breaking current Ia kA Number of operating cycles n 0 05 5 0 1 0 2 0 3 0 4 0 5 0 6 0 8 1 6 7 8 10 2 3 4 5 6 7 8 10 2 2 3 4 5 6 7 8 10 3 2 3 4 5 6 7 8 4 2 3 4 5 6 7 8 ...

Page 10: ...conductor bar A2 Front terminal for conductor bar D Pressure sensor for circuit breaker compartment F Filler connector for circuit breaker compartment K Plug Terminal for rated curreut 630 A 12 17 5 24 kV 25 kV Panel cutout View X and Y M12 25 Deep Figure 2 3 ...

Page 11: ...r for circuit breaker compartment F Filler connector for circuit breaker compartment K Plug Terminal for rated curreut 1250 A 12 17 5 kV 31 5 kV 24 kV 25 kV Panel cutout View X and Y M12 25 Deep 1 Busbar connection arranged above or bolow the breaker pole depending on the suitchgear system Figure 2 4 ...

Page 12: ...ressure sensor for circuit breaker compartment F Filler connector for circuit breaker compartment K Plug Terminal for rated curreut 1250 A 12 17 5 24 40 5 kV 31 5 kV Panel cutout View X and Y 1 Busbar connection arranged above or bolow the breaker pole depending on the suitchgear system Figure 2 5 ...

Page 13: ...r bar D Pressure sensor for circuit breaker compartment F Filler connector for circuit breaker compartment K Plug Panel cutout View X and Y 1 Busbar connection arranged above or bolow the breaker pole depending on the suitchgear system Terminal for rated current 1250 A Figure 2 6 ...

Page 14: ...25 50 120 120 74 526 10 526 84 89 127 21 83 120 62 53 8 1 8 2 2 3 8 2 3 36 17 107 8 1 5 5 2 36 61 431 104 7 232 276 5 562 1 5 130 275 1 1 130 57 2 3 2 3 57 150 150 40 20 25 50 61 125 125 125 500 10 526 83 9 21 84 89 127 21 83 46 9 62 53 8 1 8 2 2 3 8 2 3 36 17 107 8 1 5 5 2 36 61 431 104 7 50 2 562 1 5 130 275 1 1 130 57 2 3 2 3 57 150 150 40 20 25 50 A 1 Connection for conductor bar depends on sw...

Page 15: ... by a motor external activation and deactivation Emer gency manual operation with a charging lever is possible There are rating plates with the main data of the switching device at front plate 1 1 and at the right of the mounting plate 3 2 1 Operating mechanism equipment 1 Basic operating equipment Shunt release OFF Y2 Shunt release ON Y3 Mechanical ON push button 2 Mechanical OFF push button 3 Ro...

Page 16: ...tivation of the releases 1 Only shunt release OFF Y2 and Y9 and shunt release ON Y3 are provided for operational opening and closing These three releases are rotary magnets and are suitable for a high number of operating cycles 2 The undervoltage release Y4 or the indirect overcurrent release Y7 are purely safety protective tripping units and must not be used for operational switching 3 3 4 Auto r...

Page 17: ...uit breaker operating mechanism 1 1 Front plate 1 2 Bore for handling both sides 9 Mounting plate 9 1 O ring 9 2 Operating mechanism mounting 11 Insulating material pole tube 12 Breaker terminal 13 Front breaker terminal 14 Spiral spring contact 15 Vacuum interrupter 16 Contact force spring 17 Insulating push rod 18 Lock nut 18 1 Spring washer 18 2 Retaining plate 18 3 Positioning plate 18 4 Washe...

Page 18: ... Circuit breaker operating mechanism 1 1 Front plate 9 Mounting plate 9 1 O ring 9 2 Operating mechanism mounting 11 Insulating material pole half shell 12 Breaker terminal 13 Front breaker terminal 14 Flexible conductor 15 Vacuum interrupter 16 Contact force spring 17 Insulating push rod 18 Lock nut 18 1 Spring washer 18 2 Retaining plate 18 3 Positioning plate 18 4 Washer 19 Gas tight thrust bus...

Page 19: ...sh button 3 Mechanical OFF push button 4 Mechanical position indicator 5 Mechanical operating cycle counter 6 Recess for charging lever emergency manual operation 8 Mechanical charging condition indicator 9 Mounting plate 10 Breaker pole 11 Insulating material pole tube 6 Recess for charging lever 32 7 Rating plate 20 Ratchet wheel 21 Charging motor 22 Chain drive 23 Drum with spiral spring 24 Rel...

Page 20: ...echanical operating cycle counter 6 Recess for charging lever emergency manual operation 8 Mechanical charging condition indicator 9 Mounting plate 10 Breaker pole 6 Recess for charging lever 32 20 Ratchet wheel 21 Charging motor 22 Chain drive 23 Drum with spiral spring 24 Release and control mechanism on the mechanism shaft 25 Opening spring 26 Release and control mechanism area 27 Mechanism sha...

Page 21: ...rcuit breaker 35 ms tripped indication optional S10 Auxiliary switch at mechanical close push button optional Y1 Closing block magnet with rectifier V1 optional Y2 1 st shunt release off with rectifier V2 Y3 Closing release with rectifier V3 Y4 Undervoltage relay with rectifier TB6 optional Y7 Inductive overcurrent relay with rectifier V7 optional Y9 2 nd shunt release off with rectifier V9 option...

Page 22: ...ptional Y2 1 st shunt release off with rectifier V2 Y3 Closing release with rectifier V3 Y4 Undervoltage relay with rectifier TB6 optional Y7 Inductive overcurrent relay with rectifier V7 optional Y9 2 nd shunt release off with rectifier V9 optional M0 Charging motor K0 Antipumping relay R0 Resistor for antipumping relay 1 If the fitting is without blocking magnet Y1 bridge between S3 42 and Y3 C1...

Page 23: ...eration Operate the electrical control unit e g by selec ting it on the bay control and protection unit or press mechanical OFF push button 3 Switching cycle counter and switching state indicator a Operating cycle and position display on the switching device The operating cycle counter 5 is automatically incremented by one complete figure with each switching operation On completion of a switch ing...

Page 24: ...ile the work is in progress all supply voltage sources must also be disconnected and secured to prevent reconnection Note In order to prevent accidents particularly injury to hands extreme care should be taken during all repair work on the operating mechanism especially with front plate removed The spiral spring in the spring energy storage mechanism for instance retains a basic tension which is i...

Page 25: ...or replacement of highly stressed parts release the pretension of the spiral spring noting the pretensioning dimension Take care when handling springs Relubricate pawls support shafts sliding and rotating bearing surfaces Lubricant Isoflex Topas NB 52 Check the fit of fasteners e g locking pins in cranks pins bolts etc Check the tightness of fastening bolts Always replace any spring lock washers s...

Page 26: ...se original parts when replacing defective components Lubricant Isoflex Topas NB 52 Part no order code GCE0007249P0100 5 5 Spare parts and auxiliary materials 5 5 1 Auxiliary materials 5 5 2 Spare parts Designation Rotational auxiliary switch on mechanism Auxiliary switch on blocking magnet 1 st shunt release OFF 2nd shunt release OFF Shunt release ON Blocking magnet Undervoltage release Delayed u...

Page 27: ...e relevant rated power frequency withstand voltage may only be performed by trained personnel observing the stipulations of the EU basic standard Stipulation 96 29 Euratom of the senate from 13 May 1996 ABI L 159 from 29 June 1996 Application of the rated voltage specified for the switching device by VDE 0671 part 100 or IEC 62271 100 is completely safe Higher voltages than the rated voltage or DC...

Page 28: ... st Shunt release OFF Closing release Undervoltage release Indirect overcurrent release 2 nd Shunt release OFF Series rectifier for RLE1 Series rectifier for MBO1 Series rectifier for MBC Series rectifier for MBU Series rectifier for MBO3 Series rectifier for MBO2 Charging motor Anti pumping relay Series resistor Circuit breaker IEC 81346 1 IEC 81346 2 BGS1 BGL1 BGL2 BGB BGB1 BGB4 BGB7 RLE1 MBO1 M...

Page 29: ... Remarks ...

Page 30: ...n and stay connected to the latest news and tools It s a digital assistant that enables customers to connect to the broadest range of electrification solutions in one place Easy to find what you need by search Get all information about our products applications selection guides installation manuals service certificates and engineering tools etc Saving documents locally updating automatically Recei...

Page 31: ......

Page 32: ...ications subject to change without notice ABB Xiamen Switchgear Co Ltd No 885 FangShanXiEr Road Xiang an District Xiamen Fujian 361101 Tel 0592 602 6033 Fax 0592 603 0505 ABB China Customer Service Hot Line TEL 800 820 9696 400 820 9696 mail cn ep hotline abb com www abb com ...

Reviews: