3.4 Setup, data mapping and typical parameters for ACS880, DCS880
Drive Parameter
Example for ACS880, DCS880
Setup parameters
16.01 Start/Stop
N/A
20.01 Start/Stop EXT 1
Embedded fieldbus
22.11 Vector Speed Ref
EFB ref1
28.11 Scalar Speed Ref
EFB ref1
58.01 Comms Protocol
Modbus RTU***
58.03 Node Address
Drive 1,2..up to 5 *
58.04 Baud Rate
38.4 kbps***
58.05 Parity
8 EVEN 1***
58.14 Comm Loss Action
Warning
58.15 Comm Loss Mode
Any Message
58.17 Transmit Delay**
0
ACS880 typical parameters
READ from VFD
58.101 Data I/O 1
Status Word 16 bit
58.102 Data I/O 2
Act 1 16 bit
58.103 Data I/O 3
Act 2 16 bit
58.104 Data I/O 4
1.07 Motor Current
58.105 Data I/O 5
1.11 DC Bus Voltage
58.106 Data I/O 6
1.01 Motor Speed
58.107 Data I/O 7
1.14 Motor Power
58.108 Data I/O 8
1.13 Output Voltage
58.109 Data I/O 9
1.10 Motor Torque
58.11 Data I/O 10
1.06 Output Frequency
58.111 Data I/O 11
1.31 Ambient Temperature
58.112 Data I/O 12
47.21 Data Storage
Write to VFD
58.113 Data I/O 13
Control Word 16 bit
58.114 Data I/O 14
Ref 1 16 bit
58.115 Data I/O 15
Ref 2 16 bit
58.116 Data I/O 16
47.21 Data Storage
58.117 Data I/O 17
47.22 Data Storage
58.118 Data I/O 18
47.23 Data Storage
58.119 Data I/O 19
47.24 Data Storage
58.12 Data I/O 20
23.14 Acceleration time 2
58.121 Data I/O 21
23.15 Deceleration time 2
58.122 Data I/O 22
22.26 Constant Speed 1
58.123 Data I/O 23
22.27 Constant Speed 2
58.124 Data I/O 24
22.28 Constant Speed 3
58.06 Comm Control
Refresh Settings
*58.03 Node Address corresponds to the VFD-GATEWAY Node Settings (see VFD-GATEWAY Settings Web Interface)
**It is recommended to set this to 0 to avoid adding delays to the data
***The VFD-GATEWAY only supports these default settings
For ACS880 and DCS880 the write data starts at 58.113 and First 12 registers must be reads (58.101-58.112)
Note: You MUST set 58.06 to refresh settings after all parameters in group 58 are set.