M ED I U M VO LTAG E P R O D U C T S
33
33
3
2
1
3
2
1
3
2
1
3
2
1
4
3
2
4
3
2
4
3
2
4
3
2
4
3
2
4
3
2
4
3
2
4
3
2
1
1
5
5
3
3
2
1
1
on off
on off
on off
on off
on off
on off
on off
on off
on off
on off
on off
on off
on off
on off
on off
on off
on off
on off
on off
on off
Connector for the
storage capacitor/s
and the actuator coils
Power supply
connector
Connector for:
- closing pushbutton
- opening pushbutton
- luminous “READY” signal
Connector for input signal of
the circuit breaker
open/closed position sensors
Jumper only present in the full
option version.It is not normally
short-circuited and energy
consumption during capacitor
charging is 100 W.If it is short-
circuited, energy consumption
during capacitor charging is
reduced to 50 W (the charging time
is obviously doubled)
pos. 1-2:
trip input for
PR12 release
pos. 2-3:
standard opening
input
Presetting of the trip threshold for
the undervoltage function
Rated voltage
Setting
range
35% ... 70%
(Normally
preset to OFF)
220-240 V
AC / DC
84 V ... 154 V
AC / DC
100-127 V
AC / DC
45 V ... 70 V
AC / DC
48-60 V
DC
21 V ... 33 V
DC
24-30 V
DC
11 V ... 16 V
DC
Input connector:
-SO4
(1)
; -SL1; -SO3; -SO2; -SC2
ANSI self-pumping function
enabled
ANSI self-pumping function
disabled (normally preset)
Disabled (normally preset)
Automatic opening due to low energy of
the capacitor/s
Enabled (on request)
Enabling for closing with undervoltage function activated
Output connector:
DOR; DN; DR; DC2
(1)
;
DO2
(1)
; -DC1; DO1
Enabling for closing only after return of voltage at the undervoltage
input (the circuit breaker re-opens after the set delay time)
Enabling for closing with undervoltage function activated
Selector not used for the VM1 circuit breaker
(the position selected does not matter)
Safety opening disabled
Safety opening
(2)
Safety opening enabled (normally
preset)
Function
disabled(normally
preset)
No delay
Delay: 0,5 s
Presetting of the trip delay
of the undervoltage function
Delay: 1 s
Delay: 2 s
Delay: 3 s
Delay: 4 s
Delay: 5 s
7.9. Circuit breaker control card
N.B. Changing the settings by means of dip-switches must be
carried out with the control module de-energised and the
capacitor discharged since the selections set and/or modified
are acquired by the control electronics at the moment it is turned
on.
I1002-2 “off” & JP1017 “assembling”:
fast setting (10ms)
I1002-2 “off” & JP1017 “cutted”: slow
setting (20ms)
I1002-2 “on” very slow setting (43ms)
Operating time setting
With ANSI version only the Dip-switch I1001 (cally I1) for UV
thresholds adjustment is mounted on a different board:
KM1005B is to be
considered in place
of KM1005.
Fig. 13