M ED I U M VO LTAG E P R O D U C T S
31
31
Circuit breaker
VM1/P 12
VM1/P 17
VM1/P 24
VM1/W 12 (
3
)
VM1/W 17 (
3
)
PowerCube module
PB1
PB1
PB2
PB2
PB3
PB1
PB1
PB2
PB2
PB3
PB4
PB4
PB5
PB5
PB5
PB2
PB2
PB2
PB2
Standards
IEC 62271-100 •
•
•
•
•
CEI 17-1 (File 1375) •
•
•
•
•
Rated voltage
Ur [kV]
12
17.5
24
12
17.5
Rated insulation voltage
Us [kV]
12
17.5
24
12
17.5
Withstand voltage at 50 Hz
Ud (1 min) [kV] 28
38
50
28
38
Impulse withstand voltage
Up [kV]
75
95
125
75
95
Rated frequency
fr [Hz]
50-60
50-60
50-60
50-60
50-60
Rated normal current (40 °C) (
1
)
Ir [A]
630
1250
1600
2000
2500
630
1250
1600
2000
2500
630
1250
1600
2000
2500
630
1250
630
1250
Rated breaking capacity
(rated symmetrical
short-circuit current)
Isc [kA]
16
16
–
–
–
16
16
–
–
–
16
16
16
16
16
16
16
16
16
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
–
–
–
–
–
31.5
31.5
31.5
31.5
Rated short-time
withstand
current (3 s)
Ik [kA]
16
16
–
–
–
16
16
–
–
–
16
16
16
16
16
16
16
16
16
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
20
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
25
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
31.5
–
–
–
–
–
31.5
31.5
31.5
31.5
Making capacity
Ip [kA]
40
40
–
–
–
40
40
–
–
–
40
40
40
40
40
40
40
40
40
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
50
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
63
80
80
80
80
80
80
80
80
80
80
–
–
–
–
–
80
80
80
80
Operation sequence
[O-0.3s-CO-3min-CO] •
•
•
•
•
Opening time
[ms]
35...45
35...45
35...45
35...45
35...45
Arcing time
[ms]
10...15
10...15
10...15
10...15
10...15
Total interruption time
[ms]
45...60
45...60
45...60
45...60
45...60
Closing time
[ms]
50...60
50...60
50...60
50...60
50...60
Mechanical operations (cycles)
Actuator
... 100,000
... 100,000
... 100,000
... 100,000
... 100,000
Interrupters
... 30,000
... 30,000
... 30,000
... 30,000
... 30,000
Electrical operations (cycles)
Rated current
... 30,000
... 30,000
... 30,000
... 30,000
... 30,000
Under short-circuit
... 100
... 100
... 100
... 100
... 100
Maximum
overall
dimensions
H [mm]
628
628
690
690
690
628
628
690
690
690
790
790
834
834
834
632
632
632
632
W [mm]
503
503
653
653
853
503
503
653
653
853
653
653
853
853
853
503
503
503
503
D [mm]
662
662
642
642
642
662
662
642
642
642
802
802
790
790
790
664
664
664
664
Pole centre distance
P [mm]
150
150
210
210
275
150
150
210
210
275
210
210
275
275
275
210
210
210
210
Weight
<
25 kA [kg] 137
137
192
192
196
137
137
192
192
196
148
148
255
255
255
141
141
141
141
31.5 kA [kg] 144
144
192
192
196
144
144
192
192
196
–
–
–
–
–
148
148
148
148
Standardised table of dimensions
1VCD 00008
00008
00009
00009
00011
00008
00008
00009
00009
00011
00012
00012
00014
00014
00014
00074
00074
00074
00074
Operating temperature
[°C]
– 25 ... + 40
– 25 ... + 40
– 25 ... + 40
– 25 ... + 40
Tropicalisation
IEC: 60068-2-30 •
•
•
•
721-2-1 •
•
•
•
Electromagnetic compatibility
IEC 60694 •
•
•
•
(
1
) Rated uninterrupted currents guaranteed with withdrawable circuit breaker installed with air temperature of 40 °C.
(
2
) The rated normal current of 2300 A is guaranteed with natural ventilation. The rated uninterrupted current of 2500 A is guaranteed with forced ventilation.
(
3
) The circuit breakers up to 17.5 kV - 1250 A – 31.5 kA, are made with polyamide poles.
Summary of Contents for VM1
Page 59: ...MEDIUM VOLTAGE PRODUCTS 59 59 ...