Installation and commissioning guide
1ZSC000562-AAK EN, REV. 2, 2019-07-03
17
2.
Install the gasket in the groove (3) in the
transformer cover.
NOTE!
The gasket is not included in the
tap-changer delivery.
G004261
3.
Attach lifting chains (4) to the lifting eyes, and lift
the tap-changer.
CAUTION!
Make sure that the angle between the
lifting chains (4) is less than 90°.
A greater angle can cause deformation
of the lifting eyes.
G004254
4.
Carefully lower the tap-changer into the
transformer.
CAUTION!
Do not cause damage to the
terminals (5). The terminals (5) can
easily bend or break if they catch on
the transformer cover.
G004263