Installation and commissioning guide
1ZSC000562-AAK EN, REV. 2, 2019-07-03
49
5.
Make sure that the pipe (2) rises with an angle of
more than 3°.
NOTE!
If the angle of the pipe (2) is less
than 3°, air bubbles will not rise to the
oil conservator.
G004448
End of instruction
6.5 Installation of the oil tap
Overview
An oil tap must be installed för sampling of transformer oil in the tap-changer. ABB does not supply the oil
tap.
Procedure
1.
Remove the transport cover (1).
NOTE!
Keep the nuts and the O-ring.
G004446