58
Installation and commissioning guide
1ZSC000562-AAK EN, REV. 2, 2019-07-03
5.
Close the oil valve (3).
G004462
6.
Connect the vacuum equipment to the transformer.
7.
Start the vacuum equipment.
NOTE!
The vacuum is drawn from the tap-changer because it is connected to the transformer.
8.
When the vacuum is sufficient, open the oil valve
(3) on the tap-changer.
G004462
9.
Monitor the oil-level, and close the oil-valve (3) on the tap-changer at the correct oil-level.
NOTE!
Refer to
The correct oil-level,
page
10.
Release the vacuum.