Installation and commissioning guide
1ZSC000562-AAK EN, REV. 2, 2019-07-03
Protection devices and accessories
The standard IEC 60214-1 requires that at least one protection device is supplied with the tap-changer.
Protection devices must detect all faults related to the tap-changer as quickly as possible. Protection devices
operate when they detect high temperatures, high pressure pulses or high oil-flows caused by an internal
failure in the tap-changer.
The tap-changer is always supplied with a protection device, a pressure relay as standard and/or an oil-flow
relay. One of these protection devices are mandatory.
Two protection devices are available for redundancy. The tap-changer configuration is specified on the
packing list.
Protection device
Standard
Option
Note
Pressure relay
Yes
Mandatory
Oil-flow relay*
Yes
For redundancy, or as
alternative to pressure
relay.
Temperature switch
Yes
For redundancy.
Pressure relief device
Yes
For redundancy.
* The oil-flow relay is installed on the oil-conservator pipe and not shown in the figure.
G004491
Position
Flange
Designated use
1
A
Pressure relay, standard
2
B
Temperature switch, option
3
C
Empty, for oil conservator
4
D
Drain valve, standard
5
Top
Pressure relief device, option
Summary of Contents for VUBB
Page 14: ...14 Installation and commissioning guide 1ZSC000562 AAK EN REV 2 2019 07 03 ...
Page 28: ...28 Installation and commissioning guide 1ZSC000562 AAK EN REV 2 2019 07 03 ...
Page 52: ...52 Installation and commissioning guide 1ZSC000562 AAK EN REV 2 2019 07 03 ...
Page 60: ...60 Installation and commissioning guide 1ZSC000562 AAK EN REV 2 2019 07 03 ...
Page 68: ...68 Installation and commissioning guide 1ZSC000562 AAK EN REV 2 2019 07 03 ...
Page 72: ...72 Installation and commissioning guide 1ZSC000562 AAK EN REV 2 2019 07 03 ...
Page 74: ...74 Installation and commissioning guide 1ZSC000562 AAK EN REV 2 2019 07 03 ...
Page 76: ...76 Installation and commissioning guide 1ZSC000562 AAK EN REV 2 2019 07 03 ...