WavePro LT Aluminium Busway
Installation and Maintenance Manual
11
Vertical installation
For installing vertical bus run, please refer to the fig. for dimension of cut holes. It shall be ensured that the spacing between
every two runs of busway exceeds 400mm if there are two or more than two vertical runs of busway installed in the same silo.
Please refer to the Fig. below:
Fig. 2.4
When choosing the spring hangers, the elastic force should be adjusted to (G+F) kilogram (G is the weight of busbar between
each floor while F is 5~10 kilograms which refer to the on-site condition). There are mainly three types of installation:
• A. Two types for front installation of spring hangers. Please refer to the Fig 2.5.
Fig. 2.5
Wall
500
Wall
W+100
≥400
W+100
H+100
≥100