Commissioning
System Manual 2CKA000073B9795
│39
4.2.5
IP actuator
For commissioning you are located in:
Section 1 (Preparing the devices)
Overview of commissioning:
see chapter 4.1 “Overview of commissioning“
on page 30
1
Fig. 20: IP actuator: Engineering mode
To address the device, perform the following steps:
1. Activate "Engineering mode":
– After the device has booted, press button "Reset".
– The LED flashes. The flashing signals that the device is in "Engineering mode".
– If no entry is made within the next 5 minutes, the device exits the "Engineering
mode" automatically.
2. Switch to the indoor station.
Fig. 21: Addressing IP actuator