2106026MNAA | XSERIES
G 5
|
107
Table 10-1: XSeries
G5
restart options
Restart
type
Description
Use
User-triggered restart
Procedure
Warm
restart
The device:
Shuts down all
applications.
Backs up the running
data, configuration,
and logs to persistent
memory.
Restarts with running
(warm) configuration.
Automatic trigger
:
After software update
Manual trigger
:
A warm restart may be required as
part of general installation,
maintenance or troubleshooting
procedures. For example, a warm
restart restores operation if the
device is locked up due to power or
communication interruption.
10.4.2, Warm restart
with onboard RESET
button
10.4.3, Warm restart
from the device loader
10.4.4, Warm restart
from PCCU entry mode
10.4.5, Warm restart
using terminal mode
Cold
restart
The device:
Shuts down all
applications.
Deletes the running
configuration and
repopulates it using
the startup (cold)
configuration.
Restarts with startup
(cold) configuration.
Automatic trigger:
Following a startup configuration
update
Manual trigger
:
Only
as part of a service or
maintenance procedure or when
specifically directed to by ABB
technical support.
A cold restart causes running
configuration loss (which may also
include calibration files). To back
up before restart, follow
procedures in section
Preserve data and configuration
10.4.6 Cold restart with
onboard COLDBOOT
button
10.4.7 Cold restart from
the device loader
10.4.8 Cold restart from
terminal mode
Factory
restart
The device:
Shuts down all
applications.
Deletes the running
configuration and
repopulates it using
the factory
configuration.
Restarts with factory
defaults
Manual trigger
:
When it is necessary or desirable to
return the flow computer to the
original configuration as shipped
from the factory. For example: if
the device is relocated, or to start a
configuration from scratch after file
corruption or failed update.
A reset to factory defaults causes
data, running, and startup
configuration loss (which may also
include calibration files). To back
up before going back to factory
defaults, follow procedures in
section
10.4.9, Restart using the
factory configuration
Restart
due to
Power
loss
All data logs and
configurations within
the current minute are
lost.
Ensure the Lithium battery is
enabled
Power removal is
not
a
method recommended
for restart.
10.4.2
Warm restart with onboard RESET button
The warm restart resets the XSeries
G5
microprocessor. Use a warm restart to take the XSeries
G5
out of
service for maintenance or troubleshooting. Only use a warm restart when a power or communication
interruption causes the XSeries
G5
microprocessor to lock-up.
Summary of Contents for XFC G5