Figure 8-10: Constants tab
Verify or update the following:
•
For Barometric pressure, type the value, subtracted from the absolute pressure readings
when calibrating in gauge pressure.
IMPORTANT NOTE:
Barometric pressure is area-dependent. Use the correct barometric
pressure for the area or the contracted value.
•
For Orifice diameter, type the diameter in inches.
•
For Pipe diameter, type the pipe diameter in inches.
•
For Temperature base (Tb), type the value as defined by the existing contractual
agreement (default is 60 °F).
Click
Send
.
Continue to the other tabs for additional configuration if needed.
IMPORTANT NOTE:
The previous steps are the minimum requirements to get a Totalflow XFC
G5
or XRC
G5
online and measuring gas. There are many more steps depending on the site and
company requirements.
Configure and enable communication interfaces when needed:
Before configuration, wire communication or peripheral equipment to the serial communication
(COMM) terminals. See section
For remote or local network communication, note that enabling Ethernet, Wi-Fi or Bluetooth
will cause additional power consumption.
8.7.1
Configure COM1
The XFC
G5
and XRC
G5
have standard configurations with COM1 configured for remote communications
with a host. COM1 is the name associated with the COMM1 terminal. The port TF-Remote
–
COM1 is
configured to support the Totalflow Remote Protocol by default.
For additional details, click
Help
from the Communications Setup
tab
screen.
Configure COM1: