Page 2
–16
2104349 rev. AD
9) Remove the nut, sealing ring and grommet from the cord connector. Slide
the nut, sealing ring and grommet over the end of the cable, and insert the
cable through the body of the cord connector. Leave enough of the cable on
the outside of the unit to allow the cable to dip below the level of the access
hole. This provides a path for moisture to run away from the unit to the
lowest point of the cable.
10) On the inside of the enclosure, allow enough cable to comfortably extend to
the input terminals on the charger regulator (see Figure 2
11) Slide the nut, sealing ring and grommet to the cord connector on the side of
the unit, and tighten.
12) Before making connections to the charger regulator, trim the wire ends back
¼”.
13) Verify that the main battery pack is connected.
14) Loosen the securing screws on the charger regulator, insert the wire and
then retighten. Connect the solar panel (+) lead to the + terminal and the (-)
wire to the
– terminal.
15) Following the connection of the solar panel power cable, secure the cable to
the 2” extension and mounting pipe cable with the provided plastic tie-
wraps.
2.2.11 AC charging unit installation
The AC power charging unit maintains a constant voltage charge on the installed
battery pack (see Figure 2
–15).
2.2.11.1
Materials supplied
-
AC charging unit
-
Pipe nipple
2.2.11.2
Materials not supplied
-
Plastic cable ties
-
AC wiring, conduit (rigid or flexible)
To maintain system certification, all wiring must comply with
NEC 501 code and applicable ABB certification drawings.
To prevent injury, only a licensed electrician should install
AC power wiring to the user supplied primary AC power
source.
2.2.11.3
Step-by-step instructions
1) The AC charging unit is shipped separately. When the unit is received,
unpack, and inspect all components for evidence of damage. Report
damage to the shipping carrier and to Totalflow’s Service Department.
2) Remove one of the plugs from the side of the 6270 OEU so that the AC
charging unit can be mounted without obstruction. See Figure 2