5) Insert the nipple through the side of the enclosure, and install the removed
lock nut.
6) To prevent moisture from entering the enclosure after installing the AC
battery pack charger, be certain the “O” ring side of the metal backed
sealing “O” ring is against the enclosure.
7) Loosen the terminal screws, and insert the red wire into the plus (+) array
terminal and the black wire in the negative (-) array terminal (see Figure 2
17). Retighten the screws.
8) Connect the green wire to one of the grounding screws that are located on
the bottom of the enclosure.
9) Pipe the conduit and associated AC wiring into the AC charger conduit box.
The AC charger is rated at either 120 VAC 60 Hz or 240 VAC 50 Hz.
Connect the 120 V hot and neutral or the two hot wires for 240 V to the
terminals of the AC charger. Connect the ground wire to the green screw.
10) Verify that the DC power wires are terminated properly inside the 6270 OEU
cabinet and that the main battery pack plug is already connected. Apply AC
power to the AC charger.
Figure 2
–17 AC charger inside the conduit enclosure
2.2.12 Uninterrupted power supply (UPS) to the G4 EX
The G4 EX can be powered directly from any UPS that is supplying 9-30 VDC.
See Figure 2
–18 for instructions on how to wire the G4 EX termination board to a
UPS.