ABB | SACE Tmax XT
124 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Ekip Touch - Measurements | 5 - Network Analyzer
Continued from the previous page
Counters
(Sags Middle)
Description
Last time stamp
Date and time of last recording of the
Sags Middle
counter
Sags Middle
Value of last sag below the
Sags Middle [V]
threshold
Sags Long
Duration of last sag below the
Sags Middle [ms]
threshold
Actual number of S.
Sags Middle
count of the current day
Actual [day -2 ... day -7]
number of S.
Sags Middle
count of the last seven days of activity, calculated using the
internal clock of the unit
Counters
(Sags Middle)
Description
Last time stamp
Date and time of last recording of the
Sags Long
counter
Sags Middle
Value of last sag below the
Sags Long
[V] threshold
Sags Long
Duration of last sag below the
Sags Long
[ms] threshold
Actual number of S.
Sags Long
count of the current day
Actual [day -2 ... day -7]
number of S.
Sags Long
count of the last seven days of activity, calculated using the internal
clock of the unit
Swells
Certain counters relating to swells are available in the
Counters
-
Day
-
1 and Counters
-
Cumulative
submenus:
Counters
(Sags Middle)
Description
Swells Short
Counts the number of times that any line-to-line voltage exceeds the
V swell Th
Short
threshold for longer than
V swell dur Short
Swells Long
Counts the number of times that any line-to-line voltage exceeds the
V swell Th
Long
threshold for longer than
V swell dur Long
The count refers to the reference menu interval (previous day or cumulative)
NOTE:
since an event may fall under more than one category, only the counter of the main
type (long > short) is increased
Additional List
Counters
(Swells Short)
Description
Last time stamp
Date and time of last recording of the
Swells Short
counter
Last value
Value of last swell above
Swells Short
[V] threshold
Last duration
Duration of last swell above
Swells Short
[ms] threshold
Actual number of S.
Swells Short
count for the current day
Actual [day -2 ... day -7]
number of S.
Swells Short
count of the last seven days of activity, calculated using the
internal clock of the unit
Counters
(Swells Long)
Description
Last time stamp
Date and time of last recording of the
Swells Long
counter
Last value
Value of last swell above
Swells Long
[V] threshold
Last duration
Duration of last swell above
Spikes
[ms] threshold
Actual number of S.
Swells Long
count for the current day
Actual [day -2 ... day -7]
number of S.
Swells Long
count of the last seven days of activity, calculated using the
internal clock of the unit