ABB | SACE Tmax XT
172 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
External electronic accessories | 11 - Ekip Signalling 2K
Interface
the module has three signaling leds:
Figure 52
LEDs
Description
Power
Signals the on status and correct communication with Ekip Touch:
• off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module on
and communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
second): module on and communication with Trip unit absent.
I 11, I 12
Indicate the status of the contacts of each output:
• off: contact open
• on: contact closed
O 11, O 12
Indicate the status of the contacts of each input:
• off: circuit open
• on: short circuit
Menu
The specific configuration area will activate in the
Settings
-
Modules
menu if the
Ekip Signalling 2K
module
is detected correctly by Ekip Touch.
A specific menu containing the submenus of all the available and configurable inputs and outputs is available
for each
Ekip Signalling 2K
module detected by Ekip Touch.
Input parameters
All the available inputs enable the following parameters to be configured:
Parameter
Description
Default
Polarity
Defines whether the input is interpreted as ON by Ekip Touch when it is
open (
Active open
) or when it is closed (
Active Closed
)
Active
closed
Delay
Minimum activation time of the input before status change is recognized;
the delay is given in seconds and can be set within range: 0 s to 100 s, in
0.01 s steps
NOTES
:
• if the input is deactivated before this time has elapsed the status
change is not recognized
• if delay = 0 s status change must still be more than 300 µS
0.1 s