ABB | SACE Tmax XT
External electronic accessories | 13 - Ekip Signalling 3T
181 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Interface
Five signalling leds are available:
Figure 54
LEDs
Description
Power
Signals the on state and correct communication with the trip unit:
• off: module off
• on steady or flashing synchronized with the trip unit Power led: module on and
communication with trip unit present
• flashing not synchronized with trip unit Power led (two fast flashes per second):
module on and communication with trip unit absent
I 41, I 42, I 43, I 44
Indicate the state of the input contacts:
• off: input disabled
• on steady: input enabled, sensor connected and measurement valid
• flashing: input enabled, sensor not connected and/or measurement not valid
Access from the display
The following areas are activated on Ekip Touch if the Ekip Signalling 3T module is detected correctly:
•
Measurements
page, accessible from the Home page, containing the measurements of all the PT100/
PT1000 and 4-20mA Current Loop inputs of both modules 3T-1 and 3T-2
• information submenus in the
About
-
Modules
menu containing: serial number, module version and statuses
of sensors (Present/Alarm)
IMPORTANT:
•
if one or more sensors are in the alarm status, the signal on the diagnosis bar will be:
Ekip Signalling 3T
•
if a sensor is not enabled, the status indicated is: Present
Remote configurations
The configuration of the module is available:
• via Ekip Connect, with communication accessories via service connector or with communication via
system bus
• via own communication system and
Ekip Com
modules installed on circuit-breaker, in the conditions
required by the trip unit (use System Interface for details)
All the measurements, states and alarms of the module are available in both conditions.
NOTE:
parameters and measurements are distributed in Ekip Connect pages and communication
addresses sometimes nonsequential; references to the pages in Ekip Connect 3 are
given in the tables below
Enabling and measurements
The individual inputs of the modulecan be enabled in the
Ekip Signalling 3T
page: I42 Temperatures, I43
Temperatures, I44 Temperatures, I41 Current 4-20mA (per 3T-1), I52 Temperatures, I53 Temperatures, I54
temperatures, I51 Current 4-20mA (for 3T-2).
Parameter
Description
Default
Enable
Enables the specific input and relative alarm state and signaling
controls to be activated
Enabled