ABB | SACE Tmax XT
External electronic accessories | 3 - Introduction to the electronic accessories
139 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
External electronic accessories
3 - Introduction to the electronic accessories
Operating conditions
Ekip Synchrocheck,
Ekip Com
,
Ekip Signalling
and
Ekip CI
function correctly:
• In the presence of auxiliary supply voltage
• With the circuit-breaker in the Racked-in position (if the CB version is withdrawable)
The limitations listed below apply in all the other cases:
Modul /
Condition
Ekip Synchro-
check
Ekip Com
Ekip Signalling
Ekip CI
Module power
supply absent
Synchronization
contact: open
Communication:
absent
Output contacts:
open
Output contact:
maintains previous
position
CB in Test
(1)(2)
position
Synchronism: not
available
(4)
Communication:
active
Inputs and output
contacts: available
Inputs and output
contact: functioning
CB in
DISCONNECTED
(1)(3)
position
Synchronism: not
available
(4)
Communication:
partially active
(5)
Inputs and output
contacts: partial
available
(6)
Output contact:
maintains previous
position
(1)
the description refers to the module when correctly on and with the CB in the indicated position
(2)
in the Test position, the Trip unit is connected to the modules and all information is available on the display or
via external communication
(3)
in the Racked-out position, connection and communication between Trip unit and modules is interrupted.
Information is not available/valid
(4)
due to voltage not connected to the internal sockets
(5)
see System Interface, INFORMATION WITH PROTECTION TRIP UNIT DISCONNECTED section (next page)
(6)
the outputs only function correctly if configured as: input status (of module itself) or non-communication with
Trip unit. For all other configurations, the module forces the Outputs as per Contact Type parameter (NO, NC).
System Interface
Document 1SDH002031A1101.zip, describing how to use the Ekip Com communication modules correctly,
is available in ABB library; the file contains:
Document
Description
1SDH002031A1101.pdf
Guidelines with details about how to put the communication modules into
service, with reference to the protocols and supporting documents
1SDH002031A1101.xlsx
Table with the references of all the registers for parameters, controls,
measurements, etc.
The .zip file contains the files for supplementing Ekip Touch in the available communication networks, with the
specific Ekip Com module and an IMPORTANT file with notes on how to use the files:
File
(1)(2)
Protocol / Ekip Com module
ABBS0E7F.gsd + EkiDPB.bmp
File .gsd and module image for configuring
Ekip Com Profibus
DP
Ekip_COM_EtherNetIP_M4_v03_06.eds
File .eds for configuring
Ekip Com EtherNet/IP
TM
Ekip_COM_DeviceNet_v02_08.eds
File .eds for configuring
Ekip Com DeviceNet
TM
ABBEC0304_Ed1.icd
ABBEC0304_Ed2.icd
File .icd for configuring
Ekip Com IEC 61850
GSDML-V2.3-ABB S.p.A.-Ekip Com
Profinet-20180823.xml
File .xml for configuring
Ekip Com Profinet
(1)
The files are also valid for the respective Redundant versions.
(2)
Check the Firmware version of your module so as to choose the file with the correct configuration.