ABB | SACE Tmax XT

166 | © 2020 ABB |  1SDH001821A1002 - ECN000135670

External electronic accessories | 10 - Ekip Com Hub

10 - Ekip Com Hub

 

Ekip Com Hub

 is a communication accessory that enables the data and measurements of Ekip Touch and 

other devices connected to the same installation to be gathered and then made available on the server 
through an Ethernet network.
The configuration of the module is available via Ekip Connect or with the System Interface document, which 
contains all the details. (page 139).
The ports used by the module are:

Port

Service

Notes

67/udp 68/udp

DHCP client

DHCP client enabled alternatively as 

Static address

 = 

On

443/tcp

HTTPS

Always active when module is enabled

123/udp

SNTP

Active with SNTP client enabled

53/udp

DNS

Always active

The 

Ekip Com Modbus RTU

 and 

Ekip Com Modbus TCP

 modules can be configured to support 

Ekip Com 

Hub

 in the collection of data to send to Cloud. See Getting Started 

1SDC200063B0201

.

Safety and cyber security

The module uses the HTTPS protocol and can be connected to the Internet

 IMPORTANT:

• 

it is the customer's sole responsibility to provide and continuously ensure a secure 
connection between the module and customer network or any other network (as the 
case may be). The plant manager must establish and maintain appropriate measures 
(such as but not limited to the installation of firewalls, application of authentication 
measures, encryption of data, installation of antivirus programs, etc.) to protect the 
product, the network, the customer system and interface against any kind of security 
breaches, unauthorized access, interference, intrusion, loss and/or theft of data or 
information.

 

ABB and its affiliates are not liable for damages and/or losses related to 

such security breaches, unauthorized accesses, interference, intrusion, loss and/or 
theft of data or information.

Connections

The module must be assembled in the first vacant slot of the terminal box after 

Ekip Supply

, either on the 

circuit-breaker (fixed version) or on the fixed part (withdrawable version).
For references about the connection and terminals, please consult document 

1SDM000002A1001

; a cable 

of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication bus.
To connect the module to Ekip Touch, please consult document 

1SDH002009A1505

.

Power supply

Ekip Com Hub

 is supplied directly by the Ekip Supply module to which it is connected.

 NOTE: 

communication between Ekip Touch and the module is interrupted in the absence of 

auxiliary power supply

 

Summary of Contents for XT7

Page 1: ...DOC N 1SDH001821A1002 ECN000135670 Rev C SACE Tmax XT Tmax low voltage moulded case circuit breakers XT7 Operation and maintenance manual for Ekip Touch Trip Units...

Page 2: ...ABB SACE Tmax XT 2 2020 ABB 1SDH001821A1002 ECN000135670...

Page 3: ...urements 109 1 Standard Measurements 109 2 Ekip Measuring Measurements 113 3 Class 1 Power Energy Metering 116 4 Datalogger 117 5 Network Analyzer 119 Ekip Touch Settings 126 1 Main settings 126 2 Add...

Page 4: ...II 2020 ABB SACE Tmax XT 1SDH001821A1002 ECN000135670...

Page 5: ...accessories and electronic actuators connect Ekip Touch Trip unit for SACE Tmax XT7 CB equipped with touchscreen display and available in six different versions Trip coil CB opening actuator controlle...

Page 6: ...reate IMPORTANT operations which can be performed by persons trained on the subject of electricity are specifically indicated in this manual All the remaining operations described in this manual must...

Page 7: ...personnel only and is not intended to replace an adequate training course or experience concerning the safety procedures of this device regarding products equipped with communication systems the purch...

Page 8: ...erent quantities such as current voltage power energy 2 Protection depending on the measurements made and the parameters configured by the user the Trip unit checks for the presence of alarms and comm...

Page 9: ...ch is available in two versions Ekip Touch LSI and Ekip Touch LSIG Both versions have default functions and can be configured with various different additional SW packages extensions Default Functiona...

Page 10: ...ured with various different additional SW packages extensions Default Functionality Page Standard Protections 87 Standard Measurements 109 Ekip Measuring Measurements 113 Additional SW packages Functi...

Page 11: ...fault Functionality Page Standard Protections 87 Standard Measurements 109 Ekip Measuring Measurements 113 Voltage protections 53 Frequency protections 60 Power protections 1 63 Adaptive protections 7...

Page 12: ...Measurements 109 Ekip Measuring Measurements 113 Voltage protections 53 Frequency protections 60 Power protections 1 63 Adaptive protections 70 Motor protections 71 Additional SW packages Functionalit...

Page 13: ...easurements 109 Ekip Measuring Measurements 113 Voltage protections 1 53 Voltage advanced protections 1 56 Frequency protections 1 60 Power protections 1 63 Datalogger 117 Additional SW packages Funct...

Page 14: ...i Touch LSIG and has all the functions of the Ekip Touch family by default Functionality Page Standard protections 87 Voltage protections 53 Voltage advanced protections 56 Frequency protections 60 Po...

Page 15: ...183 Other external modules and accessories Name Description Page Ekip Signalling 10K 3 Programmable digital inputs outputs 186 Ekip Multimeter 3 Panel front display 187 Toroid S G R Sensor for protect...

Page 16: ...alues and monitors the plant conditions Link NOTE the link launches the software package download which requires about 1 3 Gb of space e Design ABB software suite Link which includes the following too...

Page 17: ...uct notes for Motor Protection Main features for motor protection 1SDC210112D0201 Handbook General overview of electrical installations 1SDC010002D0206 Communication functions through Ekip architectur...

Page 18: ...connected directly to Trip unit also using sockets inside the CB external transformers must be used for higher voltage values consult the chapter dedicated to the Measurement module on page 137 Ekip T...

Page 19: ...Ekip UP displays the Wizard window a user friendly procedure for immediate adjustment of certain parameters language date time voltage of the installation PIN and RELT Wizard if RELT Ekip Signalling 2...

Page 20: ...re no alarms Zone selectivity 1 Check selectivity connections between Ekip Touch and the other units as shown in circuit diagrams 1SDM000002A1001 2 Provide Ekip Touch with auxiliary power and make sur...

Page 21: ...ification of alarms check that the modules terminal box and external modules are present and connected check zone selectivity connections check opening and closing actuators NOTE the limitations and n...

Page 22: ...nch Synchronization problem of IEEE 1588 synchronization reference module MAC Address Ekip Com module detected with incorrect not allowed MAC address contact ABB Ekip Installation Installation error b...

Page 23: ...ve Th THD V above Th Single or total harmonic measurement above threshold Faults causes and remedies A list of possible faulty situations for Ekip Touch their possible causes and suggestions about how...

Page 24: ...e the rack in operation The undervoltage coil is not energized Make sure that undervoltage coil is energized properly The opening coil is permanently energized Correct operating condition If necessary...

Page 25: ...moving part and the fixed part It is not possible to lock the circuit breaker in the open position The opening pushbutton is not being pressed Press the opening pushbutton and activate the lock The l...

Page 26: ...s not present Power the trip unit with Vaux Ekip T P or Ekip TT PIN error PIN wrong or lost Contact ABB or consult document 1SDH001501R0001 Communication problems with Ekip Com Ekip Link Ekip Signalli...

Page 27: ...time t4 protetion G 400ms with CB in standard configuration UL Gext Time 400 ms Trip time t41 protetion Gext or MDGF 400ms with CB in standard configuration UL High priority alarm Modification of para...

Page 28: ...resent and other functions of the unit set parameters concerning the accessory modules connected perform tests Components The Ekip Touch interface includes a touchscreen short cut push buttons status...

Page 29: ...communication between Trip unit and Mainboard leds on with slow flashing internal error leds on and steady internal configuration error These cases need assistance from ABB Push buttons Push button De...

Page 30: ...pressing the HOME button 2 access the Alarm list by selecting the diagnostic bar at the bottom 3 access the Summary pages of some of the measurements by pressing on the edges Figure 11 NOTE Ekip Touc...

Page 31: ...US and SUBMENUS Selection of one of the level 3 menus accesses a set of submenus with the list of available options which are organized into several levels through to details of the specific parameter...

Page 32: ...details Datalogger active B Histograms of the voltage and current measurements acquired in real time The bar of each signal is represented in scale 0 to 125 with reference to the rated current and vol...

Page 33: ...lay Measuring instruments Figure 17 Depending on the Trip unit model certain measurements acquired in real time are shown on these pages by means of a pointer each page displays a specific measurement...

Page 34: ...and apparent energies 7 Ekip Signalling 3T Summary of Ekip Signalling 3T module measurements if present Ekip Touch configuration involves certain exceptions the Ne current measurements are available...

Page 35: ...wo seconds Figure 19 Select the bar to access the Alarm List page with the list of alarms present Figure 20 NOTE the Alarm List page also appears when the iTEST button is pressed in the cases provided...

Page 36: ...Menu The Protections menu can be used to configure the following protections 1 Name Parameters SW package Page L List and description in dedicated chapter Standard Protections 44 S List and descripti...

Page 37: ...r 66 ROCOF 2 List in dedicated chapter ROCOF protections 69 R STALL 2 List in dedicated chapter Motor protections 72 R JAM 2 List in dedicated chapter 72 UC 2 List in dedicated chapter 73 U 2 List in...

Page 38: ...f each phase 113 Harmonic dist Activation command for current harmonic distortion monitoring 52 Ekip Synchrocheck 2 Description in dedicated chapter 178 Network Analyzer 3 V Sequences Measurements ass...

Page 39: ...cated chapter 119 119 Datalogger 6 Enable 5 Function enabling and parameters see details in dedicated chapter 117 117 Dual Set 6 Enable 5 Function enabling and parameters see details in dedicated chap...

Page 40: ...Ekip Signalling modules are connected and detected by Ekip Touch 2 available if Ekip Touch is on with auxiliary supply 3 available with S and or S2 and or D protection enabled for S protection the se...

Page 41: ...command if present Figure 22 4 When the new value has been selected confirmed the menu of the parameter is accessed automatically the changed item presents the new value in light blue and a tick to c...

Page 42: ...ommand not to verification of the operation required which is at the user s charge whichever type of command is concerned reset parameters display open close contacts Exceptions Before validating a ch...

Page 43: ...on The PIN code is a number formed by five digits each of which can be given a value from 0 to 9 the default value is 00001 and can be changed in the Settings New PIN menu The PIN code must be entered...

Page 44: ...TRIP When the Ekip CI module is present Ekip M Touch allows a different TRIP configuration to be selected so that if a trip occurs a contact of the Ekip CI module connected to an external remote contr...

Page 45: ...h adjustable delay 46 I Instantaneous short circuit 47 G 1 Earth fault with adjustable delay 48 MCR Instantaneous short circuit on circuit breaker closing 49 2I Instantaneous short circuit programmabl...

Page 46: ...p time The value is given in seconds and can be set within the range 3 s 144 s in 1 s steps 144 s Thermal memory Activates deactivates the thermal memory function page 75 NOTE the function is always O...

Page 47: ...the thermal memory function page 75 NOTE the function is only available with curve t k I 2 OFF ZoneSelectivity Activates deactivates the function and selectivity time availability on the display page...

Page 48: ...ion The value is given in seconds and can be set within the range 0 05 s to 0 8 s in 0 01 s steps 0 05 s ZoneSelectivity Activates deactivates the function and selectivity time availability on the dis...

Page 49: ...a selectivity is activated to stimulate inputs and outputs OFF StartUp enable Activates deactivates the function and availability of the associated parameters on the display page 77 OFF StartUp Thresh...

Page 50: ...and can be set within the range 0 1 s to 1 s in 0 05 s steps NOTE in the presence of curve t k t4 can also be configured as instantaneous in this mode the trip time is comparable to that given for I...

Page 51: ...0ms Protection MCR I3 t I MCR Function The protection remains activated for a time interval running from the open closed change of status of the CB after which it deactivates If during this time inter...

Page 52: ...programmed activation event has occurred this configuration makes the function and delay parameters available Activated the protection is always activated Dependent function Function The activation ev...

Page 53: ...e trip time of the protection the value is given in seconds and can be set within a range 0 5 s to 60 s in 0 5 s steps 5 s Ekip M Touch With Ekip M Touch IU protection features the following differenc...

Page 54: ...display remains on within range 20 C 70 C All protections enabled in the unit are active in all operating states The Trip Enabling parameter can be enabled in the Settings Circuit breaker menu in ord...

Page 55: ...o check and simulate the trip times in relation to all the parameters please consult summary table of the protections with the operating characteristics page 88 the graph with trip curve page 99 Param...

Page 56: ...t t15 v UV2 Function UV2 protection functions in the same way as UV protection the protection sends a TRIP command if one or more line to line voltages detected by the unit drop below threshold U15 f...

Page 57: ...t aligned with the sequence set by the user The required sequence can be set in the Settings menu and the protection activated in the Advanced menu page 37 and page 35 VU Protection U14 t t14 V VU Fun...

Page 58: ...oltage drop varies in two different modes Step provides for a stepped variation depending on parameters Ul and Ks Lin linear provides for a dynamic variation depending on parameters Ul Uh and Ks V I20...

Page 59: ...reading Trip threshold Scal UI Ks x I20 UI I20 Lin UI Ks x I20 Ul e Uh I20 x 1 Ks x U mis Uh Uh Ul I20 Limitations and additional functions The block functions can also be accessed by means of the se...

Page 60: ...Volts and relative value Un and can be set within the range 0 2 Un to 1 Un in 0 01 Un steps 1 Un Threshold Uh2 The parameter is shown by the Lin curve and contributes towards I21 trip threshold calcul...

Page 61: ...ty in the parameters menu OFF Trip Enable Activates deactivates transmission of the open command if disabled the alarm and exceedance of protection time are only managed as information OFF Threshold U...

Page 62: ...s less than 30 V To check and simulate the trip times in relation to all the parameters please consult summary table of the protections with the operating characteristics page 88 the graph with trip c...

Page 63: ...f17 t t17 f UF2 Function UF2 protection functions in the same way as UF protection the protection sends a TRIP command if the grid frequency read by the unit drops below threshold f17 for longer than...

Page 64: ...ease consult summary table of the protections with the operating characteristics page 88 the graph with trip curve page 102 Parameters Parameter Description Default Enable Activates deactivates the pr...

Page 65: ...correctly RP Protection P11 t t11 P RP Function The protection sends a TRIP command if the reverse total active power exceeds threshold P11 for longer than t1 To check and simulate the trip times in...

Page 66: ...lt Enable Activates deactivates the protection and its availability in the parameters menu OFF Trip Enable Activates deactivates transmission of the open command if disabled the alarm and exceedance o...

Page 67: ...e displacement angle between active and apparent power measured when phase displacement exceeds the set Direction Min Angle parameter the unit considers the fault direction to have been identified The...

Page 68: ...al functions The block functions can also be accessed by means of the service connector via Ekip Connect or by connection to the system bus page 78 OP Protection P26 t t26 P OP Function The protection...

Page 69: ...ime of the protection the value is given in seconds and can be set within a range 0 5 s to 100 s in 0 5 s steps 1 s StartUp enable Activates deactivates the function and availability of the StartUp Ti...

Page 70: ...e is given as both absolute value kVAR and relative value Sn and can be set within the range 0 1 Sn to 1 Sn in 0 001 Sn steps NOTE the threshold expressed in Sn is not preceded by the sign but should...

Page 71: ...ters please consult summary table of the protections with the operating characteristics page 89 the graph with trip curve page 106 Parameters Parameter Description Default Enable Activates deactivates...

Page 72: ...t protection configurations to be made one as an alternative to the other by means of a set change with programmable events The function can be activated in the Settings Dual Set menu page 37 Paramete...

Page 73: ...time of L protection Time t1 the start up time Motor start up calculated from the moment that at least one phase exceeds the fixed threshold of 0 25 x I1 during which some protections are inhibited th...

Page 74: ...functions The block functions can also be accessed by means of the service connector via Ekip Connect or by connection to the system bus page 78 Protection R STALL Function R Stall protects against mo...

Page 75: ...page 78 Protection U Function U protects the motor in the event of phase loss the protection sends a TRIP command if the rms value of at least one phase drops below the 0 1 In threshold and at the sam...

Page 76: ...ted for the purpose of monitoring the temperature of the motor the protection sends a TRIP command if the temperature measured exceeds 120 C for more than one second Parameters Parameter Description D...

Page 77: ...as to reduce opening time IMPORTANT for the S protection the function can be activated if the selected curve is time dependent NOTE the function also reduces the trip time in the case of overloads wh...

Page 78: ...If I2 0 1 t2 sel 1 The device is in the alarm status and is the first to detect the fault trips within time t2 sel 1 If I2 1 1 t2 2 The device is in the alarm status but is not the first to detect the...

Page 79: ...t the first to detect the fault trips within time t7 Fw or t7 Bw Backward If I7 Bw x 1 x 1 t7 Bw NOTE when zone selectivity is active and the direction of the fault cannot be established the unit trip...

Page 80: ...lock active if programmable status B is true BlockOnProgStatusC Block active if programmable status C is true BlockOnProgStatusD Block active if programmable status D is true BlockOnStartUp Block acti...

Page 81: ...nfiguration is available in the Advanced menu page 35 Parameter Description Default Enable Activates deactivates the protection and its availability in the parameters menu OFF Trip Enable Activates de...

Page 82: ...ails on page 75 2 details on page78 Limitations and additional functions in the presence of curve t k I2 the protection trip time is forced to t41 if the calculation results give a theoretical value l...

Page 83: ...time availability on the display 1 NOTES the function is only available with curve t k if at least two of the selectivity G Gext and MDGF are enabled the input and output are shared with the OR functi...

Page 84: ...page 87 the graph with trip curve page 97 Parameters Parameter Description Default Threshold Idn Defines the value that activates the protection the value is given in Amperes and can be set within a r...

Page 85: ...ercentage of threshold I1 and can be set within the range 50 I1 to 100 I1 in 1 steps 50 I1 Threshold 2 I1 Enable Activates the protection and availability of the threshold in the menu OFF Threshold Th...

Page 86: ...Mode It activates 2I protection if configured for this function Advanced Functions 2I Menu 50 RESET Energy Resets the energy meters Measurements Energy 36 YO Command Sends an open command to YO Settin...

Page 87: ...if the function is enabled for S protection and is in the alarm status the S D Forward hardware block signal and the logic selectivity S bit are activated on the output depending on the block signals...

Page 88: ...if it receives the signal correctly at its input otherwise it will signal error the diagnosis check will not be performed if the hw input is active if the input configured for diagnosis is active when...

Page 89: ...Trip time t t 1 Trip threshold tolerance 3 Trip time tolerance L 49 with curve t k I 2 Activation for If within range 1 05 to 1 2 x I1 with If 6 In 10 with If 6 In 20 with curves 60255 151 S 50TD 51 t...

Page 90: ...1 5 with t12 5 s 100 ms with t12 5 s the best between 10 min 30 ms and 40 ms OF 81H OF2 87H t t t13 t18 1 5 with t13 5 s 100 ms with t13 5 s the best between 10 and 40 ms Power protections Protection...

Page 91: ...R t t ts 10 10 UC 37 t t tuc 15 20 U t t tu 8 15 20 Additional protections Protection ANSI code Trip time t t 1 Trip threshold tolerance 3 Trip time tolerance Gext 50GTD 51G t t t41 with curve t k 7 T...

Page 92: ...o be considered valid after Motor start up 8 time to be considered valid with protection in alarm status after Motor start up if the alarm appears during Motor start up the trip unit calculates and us...

Page 93: ...rated considering the minimum and maximum values and of the parameters of each protection Protections with several curves example S protection are shown in several graphs The curves do not take accoun...

Page 94: ...ABB SACE Tmax XT 92 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function L IEC 60255 151 SI Function L IEC 60255 151 VI...

Page 95: ...ABB SACE Tmax XT Protections 18 Functions 93 2020 ABB 1SDH001821A1002 ECN000135670 Function L IEC 60255 151 EI Function L t k I 4...

Page 96: ...ABB SACE Tmax XT 94 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function L Ekip M Touch Function S t k I 2...

Page 97: ...ABB SACE Tmax XT Protections 18 Functions 95 2020 ABB 1SDH001821A1002 ECN000135670 Function S t k Function S2...

Page 98: ...ABB SACE Tmax XT 96 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function I Function MCR Function 2I 18kA...

Page 99: ...ABB SACE Tmax XT Protections 18 Functions 97 2020 ABB 1SDH001821A1002 ECN000135670 Function G t k I 2 Function Gext t k I 2 Function G t k Function Gext t k...

Page 100: ...ABB SACE Tmax XT 98 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function MDGF t k I 2 Function MDGF t k 0 05 1 IEC 0 05 0 4 UL UL MAX SETTING 1200A...

Page 101: ...ABB SACE Tmax XT Protections 18 Functions 99 2020 ABB 1SDH001821A1002 ECN000135670 Function IU Function UV Function UV2...

Page 102: ...ABB SACE Tmax XT 100 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OV Function OV2 Function VU...

Page 103: ...ABB SACE Tmax XT Protections 18 Functions 101 2020 ABB 1SDH001821A1002 ECN000135670 Function S V Function S2 V Function RV...

Page 104: ...ABB SACE Tmax XT 102 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function UF Function UF2 Function OF Function OF2...

Page 105: ...ABB SACE Tmax XT Protections 18 Functions 103 2020 ABB 1SDH001821A1002 ECN000135670 Function RP Function D...

Page 106: ...ABB SACE Tmax XT 104 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function OQ Function OP...

Page 107: ...ABB SACE Tmax XT Protections 18 Functions 105 2020 ABB 1SDH001821A1002 ECN000135670 Function UP Function RQ...

Page 108: ...ABB SACE Tmax XT 106 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function ROCOF Function R JAM...

Page 109: ...ABB SACE Tmax XT Protections 18 Functions 107 2020 ABB 1SDH001821A1002 ECN000135670 Function R STALL Function UC...

Page 110: ...ABB SACE Tmax XT 108 2020 ABB 1SDH001821A1002 ECN000135670 Protections 18 Functions Function RC...

Page 111: ...ent Monitor time min max Normal operating range Accuracy of value read 1 Phase currents 4 0 004 64 In 0 2 1 2 In 1 3 Internal earth fault current 2 0 08 64 In 0 2 1 2 In 2 3 External earth fault curre...

Page 112: ...list is available in the Measurements Historicals Trips menu where useful information is given for each trip the protection that caused the trip the consecutive number of the trip the date and time of...

Page 113: ...ted recording flashes to distinguish it from the others Touch the sides of the display to select the recordings after 1 and before 2 the selected recording The command for quitting the page 3 is in th...

Page 114: ...to the last maintenance value Two areas are available in the Trip unit menu Activation area Settings Maintenance menu allows the Maintenance function to be activated Measurement and reset area Measure...

Page 115: ...and on the rated current defined by the rated size of the Trip unit In in addition the reference changes on the basis of the type of measurement Sn for total powers Sn In Un 3 Pn for phase powers Pn I...

Page 116: ...with CBs type 4P and 3P N Power Currents L1 L2 L3 Ne and total power Ne is available with CBs type 4P and 3P N Active or apparent total power depending on which protection tripped Min Max Med measure...

Page 117: ...r Energy Metering package is present and for all other Trip unit models check the indicated performance values from page 116 Energy counters The energy counters are the measurements of the total react...

Page 118: ...n 50 Hz 54 66 Hz with fn 60 Hz 5 Pmin 0 5 In x 5 V Pmax 3 x 16 In x 900 V 6 the higher phase currents are also available in the Histograms Measuring instruments and Measurement summary pages 7 the hig...

Page 119: ...analysis IMPORTANT the function requires an auxiliary voltage supply Figure 35 Parameters 1 The parameters and commands of the function are available in the Settings menu page 37 Parameter Descriptio...

Page 120: ...ip Touch maintains the registration even when off the life of the internal battery of the unit can be sensibly less than the declared value in the absence of auxiliary power supply Volatile Ekip Touch...

Page 121: ...armonic Analysis Activates harmonic analysis of the currents Off V Harmonic Analysis Activates harmonic analysis of the voltages Off V Threshold Low Control threshold of the Under V Th counter The val...

Page 122: ...ll All the thresholds are given as a percentage of rated voltage Un and can be set from 105 to 125 Un in 5 steps All the times are given in seconds and can be set within the range 0 04 s to 60 s in va...

Page 123: ...last three seconds Additional List Counters Sequences Description Last time stamp Date and time of last recording of the sequences Counters Sequences Description Last value Voltage unbalance relating...

Page 124: ...of the last seven days of activity calculated using the internal clock of the unit Counters Under Voltage Description Last time stamp Date and time of last recording of the Under V Th counter Last val...

Page 125: ...ags Certain counters relating to sags are available in the Counters Day 1 and Counters Cumulative submenus Counters Interruptions Description Sags Short Counts the number of times that any line to lin...

Page 126: ...rt Counts the number of times that any line to line voltage exceeds the V swell Th Short threshold for longer than V swell dur Short Swells Long Counts the number of times that any line to line voltag...

Page 127: ...tes THD Voltages count for the current day min Actual day 2 day 7 number of THD C THD Voltages count of the last seven days of activity calculated using the internal clock of the unit Waveforms The Ne...

Page 128: ...ks to the ABB EPiC application and the pairing configuration described in the next paragraph WARNING It is the customer s sole responsibility to provide and continuously ensure a secure connection bet...

Page 129: ...mmand which starts Pairing between Trip unit and external device To perform the operation correctly 1 Press Connect on EPiC APP select the Trip Unit from among the units in the list and then select Co...

Page 130: ...o set the installation frequency the choice is between 50 Hz and 60 Hz NOTE the measurements are taken on the basis of the set grid frequency incorrect configuration of the parameter may lead to abnor...

Page 131: ...r measurements in the event of date and time glitches reset and if necessary replace the battery inside Ekip Touch page 19 View The View menu provides various options Parameter Description Default TFT...

Page 132: ...n Mode configuration in the Normal mode if the Trip unit detects the presence of a fault even after the open command sent to O61 a command is also sent to the Trip coil of the CB Standard Autoreclosur...

Page 133: ...status activates if the trigger is present for longer than the On delay setting and de activates if the trigger is absent for longer than the Off delay setting Figure 38 The statuses can be used with...

Page 134: ...O COMMAND functions and the Request circuit breaker opening and Request circuit breaker closing commands Change Double Set of parameters always If activated enables the set of parameters Adaptive Prot...

Page 135: ...confirm the test operation An open command is transmitted to the Trip coil of the CB when the key is released IMPORTANT the open command is sent with the circuit breaker closed and in the absence of c...

Page 136: ...ch off in sequence of the two output contacts while the relative leds come on 4 Reset initial conditions IMPORTANT the Autotest command closes the contacts regardless of the configuration set by the u...

Page 137: ...4 In startup OFF Harmonic distortion On Rc 1 Idn 3 A Tdn 0 06 s 1 protection available and active if model Rc Rating Plus is present Parameters Unless different specifications are requested when order...

Page 138: ...r installation when first powered In Ekip Touch field Nom Curr in the About Circuit breaker menu displays the In quantity read by the unit Versions Various models of different sizes are available and...

Page 139: ...connection to internal terminals or in an external terminal box connection to the upper or lower terminals of the poles on the basis of the expected power flow with normal or reverse pole order For f...

Page 140: ...igh ones load connected low Low High opposite power flow load connected high High Low Neutral connection Available with 3P CB allows the presence of the external Neutral to be enabled NOTE presence of...

Page 141: ...ue to voltage not connected to the internal sockets 5 see System Interface INFORMATION WITH PROTECTION TRIP UNIT DISCONNECTED section next page 6 the outputs only function correctly if configured as i...

Page 142: ...ply present Electrical characteristics Model Ekip Supply 24 48VDC Ekip Supply 110 240 VAC DC Power supply voltages 21 5 53 VDC 105 265 VAC DC Frequency 45 66Hz Maximum power consumption without module...

Page 143: ...om Modbus RTU Redundant The modules are identical in terms of characteristics and installation methods except for display menus cabling and addresses for system communication which are specific for ea...

Page 144: ...us of the communication between network master and module slave off Modbus RTU communication not activated on with fast flashes Modbus RTU communication activated Tx Indicates the status of the commun...

Page 145: ...y bit 4 options are available 8 E 1 8 data bits 1 EVEN parity bit 1 STOP bit 8 O 1 8 data bits 1 ODD parity bit 1 STOP bit 8 N 2 8 data bits no parity bit 2 STOP bits 8 N 1 8 data bits no parity bit 1...

Page 146: ...Profibus DP Redundant The modules are identical in terms of characteristics and installation methods except for display menus cabling and addresses for system communication which are specific for eac...

Page 147: ...mination resistor Move dip switches 1 and 2 to the ON position to connect Rterm Off Rpol 3 and 4 390 pull up or pull down resistor Move dip switches 3 and 4 to the ON position to connect Rpol Off IMPO...

Page 148: ...cept for display menus cabling and addresses for system communication which are specific for each module NOTE if different indications are not given the information in the next chapter is valid for bo...

Page 149: ...Network Status 2 Indicates the communication status on the bus Off no error On fixed device in bus off or Network Power absent On flashing I O connection cyclic data in timeout 1 the device has not y...

Page 150: ...available 125 kbit s 250 kbit s 500 kbit s 125 kbit s 1 63 default of the Ekip Com DeviceNet TM module 62 default of the Ekip Com DeviceNet TM Redundant module Remote configurations Additional parame...

Page 151: ...evention measures against unauthorized access for example the network of the control system of an installation IMPORTANT it is the customer s sole responsibility to provide and continuously ensure a s...

Page 152: ...rectly by the Ekip Supply module to which it is connected NOTE communication between Ekip Touch and the module is interrupted in the absence of auxiliary power supply Interface the module has three si...

Page 153: ...Information in menu The following information will be available in the About Modules menu if Ekip Touch has detected the module correctly About Description SN and version Identifier and SW version of...

Page 154: ...onism 00 00 Daylight Saving Time Used to select whether daylight saving time is present ON or not OFF in the country to which the synchronization time refers OFF Disabilita Gratuitos ARP Permits Enabl...

Page 155: ...or example the network of the control system of an installation IMPORTANT it is the customer s sole responsibility to provide and continuously ensure a secure connection between the module and custome...

Page 156: ...module on and communication with Trip unit present flashing not synchronized with the Power led of Ekip Touch 2 fast flashes per second module on and communication with Trip unit absent Link 1 Indica...

Page 157: ...all the necessary security and prevention measures against unauthorized access for example the network of the control system of an installation IMPORTANT it is the customer s sole responsibility to p...

Page 158: ...led of Ekip Touch module on and communication with Trip unit present flashing not synchronized with the Power led of Ekip Touch 2 fast flashes per second module on and communication with Trip unit abs...

Page 159: ...IEEE 1588 protocol for distribution of the clock and synchronization signal to be enabled 1 OFF IEEE 1558 Master Enables the module to be set up as a master in the the network segment to which it belo...

Page 160: ...relative uploading procedure for assigning the Technical Name and enabling GOOSE messages if required by setting the relative MAC Addresses Depending on the parameter settings described in the next pa...

Page 161: ...breaker fixed version or on the fixed part withdrawable version For references about the connection and terminals please consult document 1SDM000002A1001 a cable of the Class 6 S FTP type Class 6 with...

Page 162: ...r Addr Allows the network server that supplies the SNTP to be set 0 0 0 0 Information in menu The following information will be available in the About Modules menu if Ekip Touch has detected the modul...

Page 163: ...disable not necessary security command TFTP always On CB Open CB Close command Defines the limitations to remote opening and closing command execution Standard commands standard commands unrestricted...

Page 164: ...Port Service Notes 18 udp ABB proprietary In the case of rapid exchanges of information among ABB devices 319 udp IEEE 1588 Valid with IEEE 1588 protocol enabled 320 udp 68 udp DHCP client DHCP clien...

Page 165: ...page 85 Connections The module must be assembled in the first vacant slot of the terminal box after Ekip Supply either on the circuit breaker fixed version or on the fixed part withdrawable version Fo...

Page 166: ...o which the modules belong and enables modules to be searched for within a defined set of recipients Gateway address IP address of the node to which the module is connected in the presence of several...

Page 167: ...d None 1 global Diagnostic Active Passive diagnosis or deactivated No diagnosis cabled selectivity diagnosis No Diagnostic Diagnostic check timeout 30 s 1 min 10 min 60 min diagnosis frequency interva...

Page 168: ...e module and customer network or any other network as the case may be The plant manager must establish and maintain appropriate measures such as but not limited to the installation of firewalls applic...

Page 169: ...s menu page 37 The following communication parameters can be configured if the module has been correctly detected by Ekip Touch in the Settings Modules menu Parameter Description Default Enable Switch...

Page 170: ...subnets MAC address Address assigned by ABB with OUI Organizationally Unique Identifier equal to ac d3 64 which uniquely identifies the manufacturer of an Ethernet device Remote configurations Additio...

Page 171: ...Name of the executable firmware update file Configuration error Module configuration error state Sample time Period of data acquisition from the connected devices Log time Period within which the acq...

Page 172: ...gnalling 2K 1 modules RELT Ekip Signalling 2K 3 The RELT Ekip Signalling 2k 3 module has a dedicated command RELT Wizard for auto programming a set of trip unit parameters The wizard ensures the activ...

Page 173: ...2 H31 and H32 for model 2K 3 must be made with reference to the common contacts HC The module permits two logic statuses interpreted differently by Ekip Touch depending on the configuration selected...

Page 174: ...t Menu The specific configuration area will activate in the Settings Modules menu if the Ekip Signalling 2K module is detected correctly by Ekip Touch A specific menu containing the submenus of all th...

Page 175: ...esent between open NO and closed NC NO Latched Allows the output and relative status led to be kept activated On or deactivated Off when the event disappears OFF min Activation Time Defines the minimu...

Page 176: ...d busbar and configuration Normal Operation with one of the voltages nil synchronism search starts if the internal voltage is 0 5 Un by default or more for at least 1 s by default synchronism is consi...

Page 177: ...l voltage Isolation transformer An isolating transformer with the characteristics given below must always be installed between the external contacts of the circuit breaker and the input of the module...

Page 178: ...set within the range 0 5 Un to 1 1 Un in 0 001 Un steps 0 5 Un Stability Time Minimum time within which the Ulive Threshold condition must be obtained in order to activate voltage monitoring The valu...

Page 179: ...en 10 of the set threshold and 0 5 Un with Un 220 V or 1 Un with Un 220V Frequency Delta the tolerance is the higher value between 10 of the set threshold and 0 02 Hz Remote configurations Additional...

Page 180: ...d by Ekip Synchrocheck measurement not available example because synchronism function is disabled or operation with dead busbar or frequencies outside measuring range limits Int Side Frequency 2 Frequ...

Page 181: ...voltage read by Ekip Touch f int frequency read by Ekip Touch phase difference SYNC status of synchronism About The About Modules menu contains the specific menu of the module with the serial number a...

Page 182: ...r resistance thermometers such as PENTRONIC TEC SITW 24F Type TX or similar Maximum length 3 meters For the 4 20mA Current Loop sensor use suitable cables up to 3 meters in length compatible with the...

Page 183: ...containing serial number module version and statuses of sensors Present Alarm IMPORTANT if one or more sensors are in the alarm status the signal on the diagnosis bar will be Ekip Signalling 3T if a...

Page 184: ...be set within the range 40 C to 240 C in 0 1 C steps NOTE the thresholds of the 4 20mA I41 and I51 Current Loop input are given in percentage form and can be set within the range 0 to 100 in 0 1 steps...

Page 185: ...pply module to which it is connected NOTE in the absence of auxiliary power supply communication between Ekip M Touch and the module is interrupted the output contact maintains its status and the inpu...

Page 186: ...th Ekip Touch off module off on steady or flashing synchronized with the Power led of Ekip Touch module on and communication with trip unit present flashing not synchronized with the Power led of Ekip...

Page 187: ...re opening command is not sent if delay 0 s the input must still be present for longer than 300 S 0 1 s Measurements The specific area of the module containing the temperature measurement of probe PT1...

Page 188: ...horized access 2 Ekip Signalling Modbus TCP Ekip Signalling Modbus TCP is an external accessory module It can be installed on a standard 35 mm DIN rail DIN EN 50022 type TS 35 x 15 mm Its function is...

Page 189: ...auxiliary supply The cable shield must be earthed on both sides of the connection Documents Further details are available in ABB Library especially in document 1SDH001000R0520 4 Rc Toroid Rc is an ext...

Page 190: ...ip AUP The communication modules are always supplied with dedicated Ekip AUP auxiliary position contacts In case of a withdrawable circuit breaker the Ekip AUP contacts give the signal of moving part...

Page 191: ...ary especially in document 1SDH001000R0519 Ekip Programming and Ekip T P Ekip Programming is a supply and communication accessory that is useful for Ekip Touch to be supplied and the tripped protectio...

Page 192: ...ABB SACE Tmax XT 190 2020 ABB 1SDH001821A1002 ECN000135670 Other electronic accessories 10 Testing and Programming...

Page 193: ...1SDH001821A1002 ECN000135670...

Reviews: