ABB | SACE Tmax XT
78 | © 2020 ABB | 1SDH001821A1002 - ECN000135670
Protections | 15 - Additional protections and functions
Startup Protection
The function, which can be activated for protections S, I, G, Gext, MDGF, S2, D and UP (if available and
enabled), allow the protection threshold (
StartUp threshold
) to be changed for a period that can be set by
the user (Startup time).
NOTE:
for UP protection, startup means the time for which the protection is disabled
The period begins after a threshold has been exceeded (activation threshold), user-programmable via Ekip
Connect or system bus, valid and verified for all phase currents.
The Startup condition elapses after Startup time and re-activates the next time the activation threshold is
exceeded
NOTE:
startup does not occur again until at least one current remains above activation
threshold level
A graphic representation with S protection follows:
Figure 32
Block functions
Six blocks can be configured for certain protections by means of the service connector (via Ekip Connect)
or communication via system bus. These blocks are useful for deactivating the protections relating to
programmable events:
Block name
Description
BlockOnProgStatusA
Block active if programmable status A is true
BlockOnProgStatusB
Block active if programmable status B is true
BlockOnProgStatusC
Block active if programmable status C is true
BlockOnProgStatusD
Block active if programmable status D is true
BlockOnStartUp
Block active during StartUp time (if StartUp for the specific protection is
available and activated)
BlockOnOutOfFrequency
Block active if frequency measured is not within 30 Hz to 80 Hz range
Each block is independent and has its own activation command (Block On); however, each protection can be
configured with several block conditions (operation in OR logic condition).
The protections which have blocks are: S, I, G, Gext, MDGF, MCR, S2, D, S(V), S2(V), UV, OV, VU, UV2, OV2,
UP, OP, RP, RQ, OQ, RV, UF, OF, UF2, OF2, ROCOF, UC, U, R Jam, R Stall.
IMPORTANT: the blocks can cause:
•
increase of protection trip times (max: + 30 ms), owing to verification of the event itself
(example: (frequency check)
•
undesired deactivation of the protection, if the block is associated with statuses or
signals to modules via local bus and auxiliary power supply is absent. In this case, it
may be useful to also consider the status of the auxiliary power supply (Supply from
Vaux) when programming the event
•
undesired deactivation of the protection, if the block is associated with frequency
measurements and the voltage is less than the minimum calculation threshold
IMPORTANT: if the function is activated, the blocks are deactivated during startup
(except for BlockOnStartup, which functions during this period)