9
Zenith Automatic Transfer Switch | new.abb.com/low-voltage
Basic Tools Needed for Installation and Maintenance
TOOL NAME
TASK(S)
17mm wrench or socket
Mechanical or compression lug installation
1/2" socket
Power cable connection
4mm and 5mm hex
Inspection of contacts - Removal of top/bottom cover
Phillips screwdriver
Removal and installation of Fascia
Inspection of ATS limit switches
Current transformers adjustments
Customer I/O adjustment
19mm wrench or socket
Mounting of Standalone ATS into enclosure
Table T3-1: Required hand tools for common installation and maintenance tasks
Table T3-1 provides a list of hand tools required to perform common installation,
operation and maintenance of the ZT30 Automatic Transfer Switch.
Torque values:
1) Power cable connectors: Refer to ATS Fascia (Front Cover)
2) All other components: Consult factory
Power Cable Connection
AMPERAGE
PART NUMBER
WIRE RANGE
1000A-2000A
2600A-3000A
Mechanical lug
S-3060
S-1529
#2 – 750 kcmil
Compression lug
PS-8419
500 kcmil
Compression lug
PS-8467
600 kcmil
Compression lug
PS-8420
750 kcmil
Table T3-2: Listing of mechanical and compression lug
AMPERAGE
DRAWING NUMBER
1000A-2000A
2600A-3000A
Mechanical lug
O-4106
O-4106
Compression lug
O-4107
O-4107