Settings
(Optional)
Time delays
Default Value
Possible range
Override momentary outage (separate for S1 and S2) 2 s
0-60 s
Transfer from S1 to S2 (separate for S2 to S1)
2 s
0-3600 s
Center-off delay
0 s
0-300 s
Generator stop
0 s
0-60 min
Set points
Voltage and frequency drop-out
±15% of nominal
±20% of nominal
Voltage and frequency pick-up
±14% of nominal
±19.5% of nominal
In-phase Monitor
Off
Off, On
Manual Retransfer
Off
Off, On
Commit Transfer
Off
Off, On
Application
S1-Transformer/
S2-Generator
See manual
Settings can be changed via the HMI as shown in Figure 6. See section 4 of the ZTG(D) O&M for further
detail. A password is required to change parameters; the default password is 00001. Alternatively,
settings can be changed with Ekip Connect 3 software using Ekip Programming module.