1
Z E N ITH Z TG ( D/C T ) T-S E R I E S 16 0 0 -3 0 0 0 A
—
2.4 Zenith ZTG (D/CT) T-series features
Feature comparison
ZTG(D/CT) (LCD screen) controls
Ampere sizes available
1600-3000A (open, delayed, & closed transition)
Rated voltage
208-480 Vac
Rated frequency
50 / 60 Hz
Phase system
Single and Three
Number of poles
2, 3, and 4
Neutral configuration
Switched
Yes
Product type
Open transition (I - II)
Yes
Delayed transition (I - O - II or II - O - I)
Yes
Closed transition (I - O - II or II - O - I)
Yes
Voltage and frequency settings
Pick up SOURCE 1 Voltage
71-99 %, 101-119 %
Drop out SOURCE 1 Voltage
70-98 %, 102-120 %
Pick up SOURCE 2 Voltage
71-99 %, 101-119 %
Drop out SOURCE 2 Voltage
70-98 %, 102-120 %
Pick up SOURCE 1 Frequency
80.5-99.5 %, 100.5-119.5 %
Drop out SOURCE 1 Frequency
80-99 %, 101-120 %
Pick up SOURCE 2 Frequency
80.5-99.5 %, 100.5-119.5 %
Drop out SOURCE 2 Frequency
80-99 %, 101-120 %
Time delay settings
Override momentary SOURCE 1 Outage, sec
0-60
Transfer from SOURCE 1 to SOURCE 2, sec
0-3600
Override momentary SOURCE 2 Outage, sec
0-60
Transfer from SOURCE 2 to SOURCE 1, min
0-120
l
ON
ll
ON
Auto
Alarm reset
AUTO
!
S1
S2
LOAD
l
ll
O
O
OFF
Esc
l
ON
ll
ON
Auto
Alarm reset
AUTO
!
S1
S2
LOAD
l
ll
Esc
Summary of Contents for Zenith ZTG T Series
Page 2: ...2 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 6: ...6 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 10: ...10 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 38: ...38 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 60: ...60 ZENITH ZTG D CT T SERIES 1600 3000 A 1 LCD ...
Page 104: ...104 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 116: ...2 116 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 120: ...2 120 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 123: ...123 1 OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...