51
O PER AT I O N , M A I N T EN A N C E , A N D I N S TA L L AT I O N G U I D E
1
LC
D
Parameters
(continued)
*Default
Device Parameters (continued)
Voltage & Frequency Setpoints
Defines the voltage and frequency limits for
source being acceptable. Source has an anomaly
when measured voltage/frequency goes out of
range drop-out lower/drop-out Upper. Source
becomes acceptable when measured voltage/
frequency goes back in range pick-up lower/
pick-up higher.
S1 Setpoints
S1 Drop-out
Voltage
Upper Threshold
102...120 % Un (115* % Un)
Lower Threshold
70...98 % Un (85* % Un)
S1 Pick-up
Voltage
Upper Threshold
101...119 % Un (114* % Un)
Lower Threshold
71...99 % Un (86* % Un)
S1 Drop-out
Frequency
Upper Threshold
101...120 % fn (115* % fn)
Lower Threshold
80...99 % fn (85* % fn)
S1 Pick-up
Frequency
Upper Threshold
100.5...119.5 % fn
(114* % fn)
Lower Threshold
80.5...99.5 % fn (86* % fn)
S2 Setpoints
S2 Drop-out
Voltage
Upper Threshold
102...120 % Un (115* % Un)
Lower Threshold
70...98 % Un (85* % Un)
S2 Pick-up
Voltage
Upper Threshold
101...119 % Un (114* % Un)
Lower Threshold
71...99 % Un (86* % Un)
S2 Drop-out
Frequency
Upper Threshold
101...120 % fn (115* % fn)
Lower Threshold
80...99 % fn (85* % fn)
S2 Pick-up
Frequency
Upper Threshold
100.5...119.5 % fn
(114* % fn)
Lower Threshold
80.5...99.5 % fn (86* % fn)
Continued on the next page
Summary of Contents for Zenith ZTG T Series
Page 2: ...2 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 6: ...6 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 10: ...10 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 38: ...38 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 60: ...60 ZENITH ZTG D CT T SERIES 1600 3000 A 1 LCD ...
Page 104: ...104 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 116: ...2 116 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 120: ...2 120 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 123: ...123 1 OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...