57
O PER AT I O N , M A I N T EN A N C E , A N D I N S TA L L AT I O N G U I D E
1
LC
D
Continued on the next page
Settings
*Default
Standard I/O Settings (continued)
Elevator pre-transfer
Signal 1
Signal is activated and transfer is delayed
according to Elevator pre-signal delay. Signal is
kept activated according to Elevator post-signal
delay after transfer.
Elevator pre-transfer
Signal 2
Signal is activated and transfer is delayed
according to Elevator pre-signal delay. Signal is
kept activated according to Elevator post-signal
delay after transfer.
Elevator pre-transfer
Signal 3
Signal is activated and transfer is delayed
according to Elevator pre-signal delay. Signal is
kept activated according to Elevator post-signal
delay after transfer.
Elevator pre-transfer
Signal 4
Signal is activated and transfer is delayed
according to Elevator pre-signal delay. Signal is
kept activated according to Elevator post-signal
delay after transfer.
Contact type
NC
Active open.
NO*
Active closed.
Modules (See Chapter 5, Electronic accessories)
System
RESET to Factory Setting
Restore default parameter values.
Date
1)
Month day, year
Time
1)
Hours:Minutes
Language
English*
Italian
French
German
Spanish
Russian
Chinese
New Password
Five digits
Temperature
Unit
Celsius*
Fahrenheit
Clock Format
24 h*
12 h
Display
Contrast
10...100 % (30 %*)
1)
Clock capacitor must be charged before inserting Date/Time. Clock capacitor is charged from source voltage (not AUX)
and takes about 10 minutes. Clock capacitor keeps the date/time saved for 48 h in case of no source voltage available.
Summary of Contents for Zenith ZTG T Series
Page 2: ...2 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 6: ...6 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 10: ...10 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 38: ...38 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 60: ...60 ZENITH ZTG D CT T SERIES 1600 3000 A 1 LCD ...
Page 104: ...104 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 116: ...2 116 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 120: ...2 120 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 123: ...123 1 OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...