72
1
Z E N ITH Z TG ( D/C T ) T-S E R I E S 16 0 0 -3 0 0 0 A
5.5.1.3 Access from the display /
Ekip Com Modbus RTU –module
With modules connected and energized
the presence of the modules on the mod-
ule slot activates additional menus on the
display. The following table illustrates the
path for accessing the configuration pa-
rameters of the modules from the display:
Settings (*Default value)
Description
:
Modules (Optional modules)
Ekip Com Modbus RTU
Serial address
1-247, default 247*
Address to be assigned to the modules.
NOTE: devices connected to the same network
must have different addresses
Baudrate
9600 bit/s, 19200 bit/s*,
38400 bit/s
Data transmission speed
Physical protocol
8.E,1*, 8.O,1, 8.N,2, 8.N,1
8.E,1 = 8 data bits, 1 EVEN parity bit, 1 STOP bit
8.O,1 = 8 data bits, 1 ODD parity bit, 1 STOP bit
8.N,2 = 8 data bits, no parity bit, 2 STOP bits
8.N,1 = 8 data bits, no parity bit, 1 STOP bit
:
—
Table 5.7 The path for accessing the configuration parameters of the Ekip Com Modbus RTU -module from the display
About
Description
:
Modules (Optional modules)
Ekip Com Modbus RTU
SN
Serial number
Version
Software version
:
—
Table 5.8 Information of Ekip Com Modbus RTU -module in HMI
The following table illustrates the path
from the display for accessing informa-
tion on the module:
Summary of Contents for Zenith ZTG T Series
Page 2: ...2 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 6: ...6 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 10: ...10 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 38: ...38 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 60: ...60 ZENITH ZTG D CT T SERIES 1600 3000 A 1 LCD ...
Page 104: ...104 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 116: ...2 116 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 120: ...2 120 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 123: ...123 1 OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...