77
1
O PER AT I O N , M A I N T EN A N C E , A N D I N S TA L L AT I O N G U I D E
—
Fig. 5.17 Signals of Ekip Com DeviceNet -module
5.5.3.1 LED indications
The following table illustrates the
possible signals, and their meaning:
LED
Indication
Description
Power LED, green
Off
Power supply absent.
On fixed Power supply and communication with the
device present.
On, with two quick flashes per second Power supply present, and communication
with device absent.
Network LED, red
Off
Device off line (with red LED off)
1)
, or in
error conditions (with red LED on).
On, fixed
Device on line, and allocated on a master
(operating condition).
On, flashing
Device on line, but not allocated on a
master (device ready for communication).
Status LED, green
Off
No error.
On, fixed Device in bus off, or Network Power absent
condition.
On, flashing
I/O connection (cyclic data) in timeout.
1)
The device has not yet sent Duplicate ID sequence on line.
—
Table 5.12 Indication / Ekip Com DeviceNet -module in HMI