O PER AT I O N , M A I N T EN A N C E , A N D I N S TA L L AT I O N G U I D E
The following table illustrates the ports
used by the module:
Port
Service
Notes
502/tcp
Modbus TCP
When the module is used as a Modbus TCP/IP communication module.
80/tcp
Server HTTP
When the module is used as a Server HTTP.
319/udp
IEEE 1588
When IEEE protocol 1588 is enabled
320/udp
—
Table 5.15 Ports of Ekip Com Modbus TCP -module
LED
Indication
Description
Power LED, green
Off
Power supply absent.
On fixed
Power supply and communication
with the device present.
On, with two quick flashes per second
Power supply present, and
communication with device absent.
Link LED, green
Off
Connection error (signal absent).
On, fixed
Correct connection.
Activity LED, yellow
Off
No activity on the line.
On, flashing
Activity present on the line (in
reception and/or transmission).
—
Table 5.16 Indication / Ekip Com Modbus TCP -module
5.5.4.1 LED indications
The following table illustrates the possi-
ble signals, and their meaning:
Link
Activity
—
Fig. 5.20 Signals of Ekip Com Modbus TCP -module
Summary of Contents for Zenith ZTG T Series
Page 2: ...2 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 6: ...6 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 10: ...10 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 38: ...38 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 60: ...60 ZENITH ZTG D CT T SERIES 1600 3000 A 1 LCD ...
Page 104: ...104 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 116: ...2 116 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 120: ...2 120 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 123: ...123 1 OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...