83
1
O PER AT I O N , M A I N T EN A N C E , A N D I N S TA L L AT I O N G U I D E
The following table illustrates the path
from the display for accessing informa-
tion on the module:
About
Description
:
Modules (Optional modules)
Ekip Com Modbus TCP
SN
Serial number
Version
Software version
IP Address
This is the address assigned to the modules at the moment of
connection to the network. It consists of four bytes (for a total of 32
bits), each of which can have value from 0 to 255. By default, allocation
is dynamic. With dynamic allocation, the modules wait to receive the IP
address from a DHCP server. Without a DHCP server, the modules adopt
an Autoconfiguration IP Address in the range 169.254.xxx.xxx,
calculated in a pseudo random manner so as to be the same at every
switch-on. Alternatively, you can enable the static IP address option,
which allows the IP address to be forced. In this case, you must make
sure that the IP Address inserted is different to that of the other
devices connected to the same network.
Network Mask
This is the subnet mask, and identifies the method to recognize the
subnet to which the modules belong, with the possibility of searching
for the modules within a defined set of recipients. If you enabled the
option Static IP Address, you must also enter the correct Network Mask.
Gateway Address
The IP address of the node to which the module it is connected, in the
presence of multiple subnets. If you enabled the Static IP Address
option, you must also enter the correct Gateway Address.
TCP Client
There are three IP Addresses of the client devices connected to the
modules.
MAC Address
It is the address assigned by ABB, having a OUI equal to ac:d3:64
1)
.
:
1)
Organizationally Unique Identifier, formed from the first three bytes of a MAC address, and which
uniquely identifies the manufacturer of an Ethernet device.
—
Table 5.18 Information of Ekip Com Modbus TCP -module in HMI
Summary of Contents for Zenith ZTG T Series
Page 2: ...2 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 6: ...6 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 10: ...10 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 38: ...38 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 60: ...60 ZENITH ZTG D CT T SERIES 1600 3000 A 1 LCD ...
Page 104: ...104 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 116: ...2 116 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 120: ...2 120 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 123: ...123 1 OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...