97
1
O PER AT I O N , M A I N T EN A N C E , A N D I N S TA L L AT I O N G U I D E
Recommended Operating / Storage Temperature
AC15
AC12
AC13
Ue/[V]
Ie/[A]
Ue/[V]
Ie/[A]
P/[W]
Ie/[A]
P/[W]
230
6
24
10
240
2
50
400
4
72
4
290
0.8
60
415
4
125
2
250
0.55
70
690
2
250
0.55
140
0.27
440
0.1
44
—
Table 7.2 Technical data for auxiliary contacts according to IEC 60947-5-1, for OA1G_, OA3G_
Environmental
Value
Operating temperature
-20… +65 °C
Transportation and storage temperature
-20… +75 °C
Altitude
Up to 2000 m
—
Table 7.3 General technical data of automatic transfer switch
Type
Voltage
[Vac]
Nominal
current*
[A]
Contact transfer
time
1
I-II or II-I
[ms]
ZTG 1600-3000 A
200 - 480
40-45
<75
ZTGD 1600-3000A
200 - 480
65
<75
ZTGCT 1600-3000A
200 - 480
65
<75
1
Under nominal conditions
2
All times consider that all timers are set to "0"
—
Table 7.4 Specified technical data of operating times
Do not store the automatic transfer
switch in corrosive environments above
LC1 (sea salt mist) and G1 as per ANSI/
ISA-S71.04-1985. Failure to comply with
these instructions may result in product
damage. Store the automatic transfer
switch and related accessories in a clean,
dry location in their original packaging.
Summary of Contents for Zenith ZTG T Series
Page 2: ...2 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 6: ...6 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 10: ...10 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 38: ...38 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 60: ...60 ZENITH ZTG D CT T SERIES 1600 3000 A 1 LCD ...
Page 104: ...104 1 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 116: ...2 116 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 120: ...2 120 ZENITH ZTG D CT T SERIES 1600 3000 A ...
Page 123: ...123 1 OPER ATION MAINTENANCE AND INSTALL ATION GUIDE ...