Manual ZX0 HB 600 en - Revision 05 |
73
1)
Higher ambient temperature on request
2)
Panels without auxiliary power supply: -25 °C
3)
Greater site altitudes on request
4)
Take suitable action to prevent condensation in the low voltage compartment.
5)
Additional measures required (on request)
Table 10.3: Panel weights
Panel type
Panel width
[mm]
Rated current
[A]
Weight, max.
[kg]
Outgoing feeder panel with circuit-breaker
400
...800
300
600
...1250
600
Outgoing feeder panel with three position switch-disconnector
400
...800
225
Outgoing feeder panel with three position switch-disconnector and fuse
400
...800
280
Sectionalizer panel
400
...800
390
600
...1250
600
Riser panel
400
...800
335
600
...1250
550
Metering panel
400
300
Busbar earthing panel
400
195
Table 10.2: Operating conditions
Ambient temperature, maximum
°C
+40
Ambient temperature, maximum 24 h average
1)
°C
+35
Ambient temperature, minimum
2)
°C
-5
Site altitude
3)
m
...1000
Average humidity measured over 24 h
4)
%
≤ 95
Average relative humidity in one month
4)
%
≤ 90
Ambient air
Ambient air not significantly contaminated by dust, smoke,
corrosive or flammable gases or salts.
Seismic withstand capability
5)
Tested to IEEE Std. 693 Draft 6,