background image

www.abelko.se

Power supply

UltraBase40 can be powered in several ways. Requirements and characteristics 

of the unit’s inputs and outputs can be found in the table below. 

Port

Supply

Supply expansion 

module 

(port Ex)

24 V out 

(port Out)

(out +12V)

    (in 

+12V

**) 

12 VDC* (>300 mA)

  No

No

Not 

available

VDC

 

24 VDC* (>300 mA) 24 VDC, 1A

24 VDC, 

100 mA

12 VDC, 

100 mA

24V

24 VAC (>300 mA)

No

No

12 VDC,  

100 mA

24 VDC* (>300 mA)

No

No

12 VDC, 

100 mA

 

* Stabilized DC voltage. 

** Use 

GND

 from the port 

Out

.

The 

Power

 LED lights up when the device is energized and the 

Status

 LED 

lights up when the device has started up and is working. 

Safety instructions

All external equipment connected to the device must have double or 

enhanced isolation (class II) from power mains or other dangerous 

voltage source (>50 VAC or > 75 VDC).

Note that all cables used must be approved for at least 50 °C ambient 

temperature.

At high ambient temperatures there is a risk for burning injuries. Wait 

for the equipment to cool down, and use protective gloves.

Network connection

The unit is connected to a permanent network by the 

Ethernet

 port. The 

factory default IP address is 

10.0.48.94.

Local PC 

is used only to connect the unit directly to a PC. It has IP address 

192.168.142.1

, and can be used to configure the regular network connection 

in the UltraBase40.

When you use the 

Local PC

 port, the computer should be configured for 

DHCP

 

(which it usually is). 

1.  Open a web browser and enter the IP address https://192.168.142.1 in 

the address bar. This will take you to the login page. 

 

 

User name and password the first time you log in:

Reviews: