www.abelko.se
Power supply
UltraBase40 can be powered in several ways. Requirements and characteristics
of the unit’s inputs and outputs can be found in the table below.
Port
Supply
Supply expansion
module
(port Ex)
24 V out
(port Out)
(out +12V)
(in
+12V
**)
12 VDC* (>300 mA)
No
No
Not
available
VDC
24 VDC* (>300 mA) 24 VDC, 1A
24 VDC,
100 mA
12 VDC,
100 mA
24V
24 VAC (>300 mA)
No
No
12 VDC,
100 mA
24 VDC* (>300 mA)
No
No
12 VDC,
100 mA
* Stabilized DC voltage.
** Use
GND
from the port
Out
.
The
Power
LED lights up when the device is energized and the
Status
LED
lights up when the device has started up and is working.
Safety instructions
All external equipment connected to the device must have double or
enhanced isolation (class II) from power mains or other dangerous
voltage source (>50 VAC or > 75 VDC).
Note that all cables used must be approved for at least 50 °C ambient
temperature.
At high ambient temperatures there is a risk for burning injuries. Wait
for the equipment to cool down, and use protective gloves.
Network connection
The unit is connected to a permanent network by the
Ethernet
port. The
factory default IP address is
10.0.48.94.
Local PC
is used only to connect the unit directly to a PC. It has IP address
192.168.142.1
, and can be used to configure the regular network connection
in the UltraBase40.
When you use the
Local PC
port, the computer should be configured for
DHCP
(which it usually is).
1. Open a web browser and enter the IP address https://192.168.142.1 in
the address bar. This will take you to the login page.
User name and password the first time you log in: