6 Commissioning
ABICOOLER 1300
6 Commissioning
6.1 Fuse protection for the device
► Device (115 V and 230 V) with a T2A fuse (5 × 20 mm).
WARNING
W
Electric shock due to defective cables
Damaged or improperly installed cables can lead to fatal electric shock.
► Check all live cables and connections for proper installation and damage.
► Damaged, deformed or worn parts should only be replaced by a qualified electrician.
NOTICE
Material damage due to contaminated coolant
Contamination in the coolant can lead to damage and increased wear in the device.
► Keep the coolant tank cap closed.
► We recommend that you use a coolant filter (not included in the scope of supply).
NOTICE
Material damage due to a lack of coolant
If there is insufficient coolant, the device's pump can overheat and cause irreparable damage.
► Ensure that coolant is added to the device before commissioning it.
► Ensure that the device is bled during commissioning.
► Ensure that the coolant pump does not run dry.
► Observe the fill level indicator on the device.
► Use the flow control to continuously monitor the proper function of the entire cooling system. If the flow
rate is too low, the flow control instigates the immediate switch-off of the connected devices and
prevents thermal overload.
NOTICE
Material damage when bridging multiple devices
The use of several devices (in sequence or in parallel) can result in material damage.
► Do not bridge the device with other cooling units.
Fig. 5
Fuse protection
A
Fuse
A