2.

 

Check Battery LE

D

 (

)

: 

˙

  Red LED flashes every 0.5 seconds and buzzer alarms every 0.5 seconds when UPS is in battery 

low condition. 

3.

 

Main Switch

: 

˙

  To Control on/off the UPS when Utility is normal. 

˙

  To enable “DC-Start” Function when Utility fails. ( To enable DC Start properly, you are 

recommended to connect <80% output load with the UPS only) 

……………………………………………………………………………..…………………………

 

ABLEREX 1000L / 1500L 

1. Line LE

D

 (

)

: 

˙

  Green LED remains standstill when Utility is normal. 

˙

  Green LED flashes every 2 seconds when the UPS is in Battery 

charging mode. 

˙

  Green LED remains standstill and simultaneously buzzer alarms   

continuously when the UPS is in overload condition. 

2. Inverter LED (

)

 

˙

  Yellow LED flashes every 2 seconds and simultaneously buzzer alarms continuously when Utility 

failure. 

3. Overload LED (

˙

  Red LED remains standstill and simultaneously buzzer alarms continuously when the UPS is in 

overload condition. 

4. Check Battery LED (

˙

  Red LED flashes every 0.5 seconds and buzzer alarms every 0.5 seconds when UPS is in battery 

low condition. 

5. Main Switch

 

˙

  To Control on/off the UPS when Utility is normal. 

˙

  To enable “DC-Start” Function when Utility fails. (To enable DC Start properly, you are 

recommended to connect <80% output load with the UPS only) 

NOTE

  Make sure the computer connected to the UPS is switched on before enable the "DC-Start" 

function. You are not recommended to add some other computer or peripherals after DC-Start function 

is activated.

 

REAR  PANEL  EXPLANATION

 

1. AC Inlet

                         ABLEREX 625L

 

2. Backup Outlets

3pcs NEMA5-15R or IEC320 

3. USB Interface. 
4. RJ11/RJ45 Jacks

MODEM /LAN Protection   

5. Site Wiring Fault Indicator

For 115Vac system only. 

6. AC Fuse Holder. (W/fuse)

625VA/115Vac/8A and 

625VA/230Vac/6.5A 

……………………………………………………………

 

1. AC Inlet                                             

ABLEREX 1000L / 1500L

 

2. Backup Outlets

6pcs NEMA5-15R, Local socket or IEC320   

3. Computer Interface

True RS232 communication port. 

4. RJ11/RJ45 Jacks: MODEM /LAN Protection 
5. Site Wiring Fault Indicator: For 115Vac system only. 
6. USB Interface. 
7. Fuse.

 

1

2

3 4

5

AC INP UT

IN

OUT

USB

 

AC  INP UT

IN

OUT

U SB

AC   IN P UT

IN

OUT

USB

REPLACING THE BATTERY

 

NOTE

Once the battery is disconnected, the loads are not protected from power outages. 

ABLEREX 625L

 

Use a cross-type screwdriver to remove the two 
front panel screws and slide down the panel. 

ABLEREX 1000L / 1500L

 

Use a cross-type screwdriver to remove the two 
top cover screws and slide back the cover. Please 
refer to the figures STEP 1 through STEP 4.

 

 

1.

 

Gently Pull the battery out of the UPS. 

2.

 

Loosen the black wire from the negative (-)    terminal   

and red wire from the positive (+) terminal. 

3.

 

Connect the battery leads to the new battery. 

Note

Small sparks at the battery connectors are normal during connection. 

4.

 

Slide the battery into the UPS. 

5.

 

Close the front panel and fasten two screws. 

6.

 

Dispose of the old battery properly at an appropriate recycling facility. 

 

TROUBLE SHOOTING

 

Situation Check 

Items  Solution 

Mains normal but 'Line'

 

LED 

is not on. 

1.

 

Is the power switch on? 

2.

 

Is the fuse in order? 

3. Is the power cord loose? 

1.

 

Press Main Switch on. 

2.

 

Change fuse w/same rating. 

3.

 

Re-connect the power cord 
properly. 

'Line' LED flashes every 
second but no output 

Battery voltage is too low 

Recharge the UPS for 24 
hours.  

Alarm buzzer beeps 
continuously when Utility is 
normal.  

Check to see load status if it is 
in overload. 

Remove some uncritical load. 

Alarm buzzer beeps for 10 
seconds, then the UPS is 
turned off 

 

Remove some uncritical load 
and re-switch on the UPS.   

No LEDs display on the front 
panel 

 

Consult with your sales agent 
for help. 

UPS dose not provide 
expected back up time. 

1.

 

The UPS’s battery is weak 
due to recent outage. 

2.

 

The UPS’s battery is near 
the end of its service life. 

1. Charge the battery. 
2. If the battery is near the end 

of its service lift, consider 
replacing the battery. 

The UPS operates normally, 
but the site wiring fault 
indicator is lit. 

Building wiring error such as 
missing ground or hot to 
neutral wire reversal. 

Have a qualified electrician 
correct the building wiring. 

Automatic Shutdown Software can be downloaded at www.ablerex.com.sg 