18
Section5 describes how to use the monitoring platform. Please read carefully
before use.
If grid power is turned on but MAINS INPUT is not active, grid power will
already be passed through AUX to the SCR. This means the machine is
powered and the casing should be kept closed to prevent electrocution.
4.2.1.
Mains power normal boot mode
Monitoring Software
Touch Panel
Turn on the MAINS INPUT switch on the front panel. The relays and
magnetic contacts in the UPS module will activate in series under normal
boot conditions. The touch panel or monitoring software will display the
tri-phase input voltage, current and frequency return values. The INV in the
system is not yet activated at this point but the DC Bus within the UPS
module is already at high voltage and represents an electrocution hazard.
Next, on the touch panel select Main
→
Command
→
Operation
→
Normal
Mode, or from the monitoring software select Home
→
Command
→
Normal
Mode as pictured above to activate INV. The touch panel or monitoring
software will now display the UPS output readings and status on the main
screen or view page. At this point, the Normal booting process with grid
power is complete.
19
4.2.2.
Battery boot mode
Monitoring Software
Touch Panel
BRIC30S/BRIC30N offers a Cold Start kit that allows the UPS to boot
directly from the battery when grid power fails.
Check that the battery capacity and quantity matches the UPS
requirements.
On the touch panel select Main
→
Command
→
Operation
→
Cold Start
precharge ready, or from the monitoring software select Home
→
Command
→
Cold Start precharge ready as pictured above. The
electromagnetic relays in the Cold Start kit will make a sound when the
conditions are met. Once the system has been successfully booted, the
touch panel or monitoring software will display the system status. The
Battery mode boot process is then complete.
4.2.3.
Shutdown
Monitoring Software
Touch Panel