10
3.3.
Electrical Installation
3.3.1.
BRIC30S/BRIC30N uses a plug and play design for the power input.
Grid power can be connected to the connector kit to power female
socket. When the UPS module is connected to the connector kit, power
becomes available. The power supply installation of the connector kit is
as shown below:
Attention: For safety reason, please plugging machine is carried
out by technicians.
Attention: Phase direction
→
L11/L21/L31 is indicated phase R;
L12/L22/L32 is indicated phase S and L13/L23/L33 is indicated
phase T.
11
3.3.2.
BRIC30S/BRIC30N offers two installation methods for connecting
external UPS power sources: single-loop or dual-loop:
Single-Loop
BRIC30S schematic diagram
BRIC30N schematic diagram
In a single-loop setup, the MANUAL BYPASS, AUX and MAINS use
the same input source. The input must have a common connection
between the AUX and MAINS ports. In single-loop mode, we strongly