Maximum Current
Input/Output
Voltage
Output Power
Maximum
Input
Current
(1)
Max.
Output/Bypass
Input Current
(2)
Max. Battery
Discharge
Current
(3)
380 V
10kVA/10kW
19 A
15 A
35 A
20kVA/20kW
38 A
30 A
69 A
30kVA/30kW
57 A
46 A
103 A
40kVA/40kW
75 A
61 A
137 A
60kVA/60kW
113 A
91 A
206 A
80kVA/80kW
150 A
122 A
274 A
400 V
10kVA/10kW
18 A
14 A
35 A
20kVA/20kW
36 A
29 A
69 A
30kVA/30kW
54 A
43 A
103 A
40kVA/40kW
72 A
58 A
137 A
60kVA/60kW
108 A
87 A
206 A
80kVA/80kW
144 A
116 A
274 A
415 V
10kVA/10kW
17 A
14 A
35 A
20kVA/20kW
35 A
28 A
69 A
30kVA/30kW
52 A
42 A
103 A
40kVA/40kW
69 A
56 A
137 A
60kVA/60kW
104 A
83 A
206 A
80kVA/80kW
138 A
112 A
274 A
(1)
The UPS is operating at rated voltage, rated power and batteries are charging but regardless of the
overload.
(2)
The UPS is operating at rated voltage and rated power but regardless of the overload.
(3)
12Vbattery blocks × 32pcs. The UPS is operating at rated voltage and rated power but regardless of
the overload.
Recommended Size of Cables
Capacity
Mains Input
(1)
Output/Bypass Input
(1)
External Battery
(1)
R/S/T/N
PE
R/S/T/N
(2)
PE
+/-/N
PE
10kVA
5 mm
2
3 mm
2
5 mm
2
3 mm
2
8 mm
2
3 mm
2
20kVA
8 mm
2
5 mm
2
6 mm
2
5 mm
2
16 mm
2
8 mm
2
30kVA
16 mm
2
8 mm
2
13 mm
2
8 mm
2
30 mm
2
10 mm
2
40kVA
25 mm
2
10 mm
2
20 mm
2
10 mm
2
50 mm
2
16 mm
2
60kVA
40mm
2
16 mm
2
35 mm
2
16 mm
2
70 mm
2
25 mm
2
80kVA
50mm
2
20 mm
2
40 mm
2
20 mm
2
100 mm
2
32 mm
2
(1)
The recommended maximum length of cabling is less than 10meters.
(2)
Please over size neutral line N by 1.7 times of the phase line for non-linear loads.
26