7.
Technical Specification
Capacity
10 kVA
20 kVA
30 kVA
40 kVA
60 kVA
80kVA
Input
Voltage
400V 3 Phase + N
Voltage Tolerance
±20% @100% load, -40% ~-20% @50% load
Frequency
40 ~ 70Hz
Power Factor
≧
0.99
THDi
<3%
Output
Voltage
380/400/415V 3 Phase + N
Voltage Tolerance
±1% (Static Load)
Frequency
50/60Hz
Frequency Tolerance
±0.01% (free running)
Power Factor
1.0
Crest Factor
3:1
Voltage Harmonic
Distortion
≦
1% with linear load;
≦
3% with distorting load
Overload
110% for 60 minutes, 125% for 10 minutes, 150% for 1minutes
(<105% overload continuously without alarm, >= 105% <110% continuously with alarm)
Parallel
Up to 6 units
Bypass
Voltage
380/400/415V 3 Phase + N
Voltage Tolerance
Preventive range ±10% (Adjustable ±5% ~ ±15%)
Critical range ±25% (Adjustable ±16% ~ ±30%)
Frequency
50/60Hz
Frequency Tolerance
±1Hz / ±3Hz (Selectable)
Battery
Number of batteries
12V,32
(1)
/34/36/38/40pcs configurable
Charging
Current
(2)
100%
Load
3.5 A
7 A
10 A
13 A
20A
26 A
80%
Load
7A
14A
(2)
20A
(2)
26A
(2)
40A
(2)
52A
(2)
Common Battery for
Parallel Configuration
Yes
Internal Battery
Available for housing 12V 7/9Ah 40pcs x 2 strings
N.A.
Maximum Efficiency
VFI Mode
>94%
>94%
>95%
>95%
>95%
> 95%
ECO Mode
>98%
Backup Mode
>93%
>93%
>94%
>94%
>94%
> 94%
(1)
80kVA with 32pcs batteries less than 10min. backup time
(2)
To increase the charging current please refer to your sales contact
57