 DA430 SWING DOOR OPERATOR

– Installation and commissioning manual

Summary of Contents for DA430

Page 1: ...An ASSA ABLOY Group brand ABLOY DA430 SWING DOOR OPERATOR Installation and commissioning manual ...

Page 2: ...ols Frequently examine the installation for imbalance and sings of wear or damage to cables springs and mountings Do not use if repair or adjustment is necessary Disconnect the supply when cleaning or other maintenance is being carried out Before installing the operator check that the operator is in good mechanical condition and it opens and closes properly Ensure that entrapment between door and ...

Page 3: ...perator and sliding arm DC194 to the opening side 12 7 INTERNAL CONNECTIONS 13 8 COMMISSIONING 14 9 A SAFE DOOR 16 10 EXTERNAL CONNECTIONS 17 11 CONNECTION EXAMPLES 18 11 1 Safety sensors DA001 and DA002 18 11 2 DA061 and DA062 Microwave motion sensor 19 11 3 DA063 Microwave motion sensor 19 11 4 DA033 Elbow switch 20 11 5 DA039 and DA049 rotary switch 20 11 6 Electric locks EL402 EL404 EL502 21 1...

Page 4: ...4 1 REVISION Following pages have been revised Page Revision As at 21 09 2009 ...

Page 5: ...6x16 4 pcs grooved spindle 1 pcs tension sleeve 1 pcs DA105 Mounting plate screws 5 5x32 6 pcs ordered separately DC190 Standard arm screw M6x16 1 pcs screws M5x12 Poz 2 2 pcs screws 4 8x32 Poz 2 2 pcs ordered separately DC194 Sliding arm screw M6x16 1 pcs screws M5x40 Poz 2 2 pcs screws 4 8x60 Poz 2 2 pcs ordered separately ...

Page 6: ...nductive load Features Swing door operator for indoor use only Door weight up to 80 kg standard arm and 60 kg sliding arm Low noise Compact design easy to install Low resistance if manually used Push Go Adjustable hold open time 0 60 s or sequential use Built in 24 VDC 0 5 A power supply for external devices Secondary DC inlet power back up 24 VDC 2A Maximum opening angles With standard arm DC190 ...

Page 7: ...is restrained during that time After that the operator tries to open the door If the door is still obstructed in the same position after 4 trials operator closes the door Obstructed closing The door is set free for After that new trial is done to close the door Maximum amount for trials is 4 If it is exeeded the door is set free for 1 minute Atfter this new trial is done to close the door 4 OPERAT...

Page 8: ...ting Connecting impulse devices Preparing installation Check the correct function of the door Hinges Door clearance Check the correct function of the lock Lock case Striker plate Suitability of the lock s function Removal of housing Note Remove the protective earth wire from cover and connect it back after installation Ensure the mains disconnected when removing or re fitting the cover ...

Page 9: ...rely fix the operator or the mounting plate to the transom Minimum requirement for wall profile is 5 mm steel Installing the operator Installing the mounting plate DA105 The mounting plate DA105 with the door operator ensures the installation base is level Use the mounting plate if needed 0 261 86 15 0 66 55 33 11 522 436 Ø 22 44 210 261 5 399 479 0 44 Hinge line 10 9 ...

Page 10: ...10 6 2 Assembly of the operator and standard arm DC190 to the closing side 20 42 Min 21 Max 32 340 Ø 6 Hinge line The measure from bottom of the operator The measure from bottom of the frame 80 68 ...

Page 11: ...M Min 22 Min 29 Max 40 The measure from bottom of the operator The measure from bottom of the frame Frame depth H mm DA430 distance from hinge line Arm distance L mm Minumum door width M mm 0 20 0 170 675 20 40 40 130 635 40 80 40 125 630 80 100 40 115 620 80 Frame depth H 68 Min 2 ...

Page 12: ...ening side Min 29 Max 40 Min 12 23 M 485 L Hinge line The measure from bottom of the operator The measure from the top of the door Frame depth H mm Arm distance L mm Minumum door width M mm 0 40 184 690 40 100 210 715 100 150 236 740 32 5 Frame depth H 68 80 Min 10 ...

Page 13: ...l unit s motor control components No battery charging or maintenance is provided by DA430 7 INTERNAL CONNECTIONS Electrical connections should be made by a qualified electrician The power plug or an optional external switch must have an easy access The concealed mains installation must be equipped with an external switch providing all pole disconnection Keep the mains disconnected during installat...

Page 14: ...nsure the proper function of the lock when prepull is needed small medium large sealed custom DOOR Jumper in block Custom together with S M or L gives you more power S Custom force between S and M M Custom force between M and L L Custom force more than L 6 Check the PREPULL 0 5 s 1 0 s 1 5 s Push Go PREPULL PREPULL 0 5 s 1 0 s 1 5 s Push Go For Sealed it is possible to select different prepull tim...

Page 15: ...7 3 2 1000 3 4 4 0 1200 4 1 4 7 1300 4 5 5 1 Minimum safe opening and closing times for door of various widths and weights are summarized in the table 19 Test the operation Note Long hold open time increases the safety of the door Turn mode switch to AUTO Test the operation If the function is not as desired turn mode switch to MAN and repeat steps 4 10 Resetting operator to factory settings operat...

Page 16: ...oor operates smoothly but equally does not have excessive force for the application In all cases the door size should be set to the smallest possible setting S small M Medium L Large remembering the half steps achievable with the custom setting we effectively have S S M M L L We should always remember that these force setting also has an effect with the inbuilt safety settings i e the more force a...

Page 17: ...e event of an open circuit it will prevent a potentially unsafe door opening The safety sensor is active for the first 70 of the door opening it will not stop the door opening when it has passed the 70 point because it has been designed so that it can ignore any obstacles like the door reveal or walls running in parallel to the door opening angle The resistor between terminals 1 and 4 must be left...

Page 18: ... operator This cable is vulnerable due to the door s movement and in the event of an open circuit it will prevent a potentially unsafe door opening When sensor detects an obstacle the operator stops the door When sensor detects an obstacle the operator opens the door for duration of the hold open time 1 2 3 4 5 6 7 8 1000 ohm 24V out GND Impulse input Safety sensor Locking circuit GND 1 2 3 4 5 6 ...

Page 19: ... circuit GND 1 2 3 4 5 6 7 8 9 1000 ohm yellow green white brown blue pink 1 2 3 4 5 1000 ohm 24V out GND Impulse input Safety sensor Locking circuit GND 1 2 3 4 5 6 7 8 9 11 2 DA061 and DA062 Microwave motion sensor 11 3 DA063 Microwave motion sensor ...

Page 20: ...20 COM N O N C 1 3 2 11 4 DA033 Elbow switch 11 5 DA039 and DA049 rotary switch red blue black ...

Page 21: ...mpulse input Safety sensor Locking circuit GND 1 2 3 4 5 6 7 8 9 11 6 Electric locks EL402 EL404 EL502 11 7 Motor locks EL490 EL590 NOTE Not to be installed in doors with seal force Bolt and trigger bolt have to be lubricated when lock is installed and when necessary black blue green red grey blue green white red ...

Page 22: ...CKUP BACKUP WHITE YELLOW GREY RED BROWN BLUE ORANGE TURQUOISE PINK S N 1 EA420GREEN BLACK VIOL 1 2 3 0 0 0 0 0 1 0 1 0 0 1 1 1 0 0 1 0 1 1 0 1 1 1 2s 3s 4s 5s 6s 8s 12s 15s TIME RED GREEN RESERVED NC NO NO NC NO NC DELAY SWITCH 0 1 2 4 3 1 Example 3s 12 24VDC 12 18VAC 12V GND Extension cable ABLOY EA218 EL219 Cable 16 x 0 14 mm 2 Length 6m 10m EA218 1000 ohm 11 8 Motor locks EL420 EL520 11 9 Elect...

Page 23: ...open and close positions 2 Check all impulse devices and connections G lit Y flash Flash short short short 1000 ohm resistor is missing or cable of safety sensor is cut Flash short long short long Safety sensor is active or cable of safety sensor is short circuited 1 Check that 1000 ohm resistor is connected in control board or in safety sensor 2 Check that cables are not damaged 1 Move obstacle f...

Page 24: ...ly and locking works well Regular annual services are made Under 100 openings per day service once a year 100 500 openings per day service two times a year Inspections made in service Fixing of the operator and arm Function and adjustments of impulse and safety devices Programming and adjustments of the operator Movement of the door taught door positions ...

Page 25: ...25 14 SPARE PARTS Cover aluminium 410370 Cover white 410369 Head panel 813319 Compatible unit 813486 Position sensor 806811 Control unit 813465 Transformer 806903 Mode switch 806914 DC194 DC190 ...

Page 26: ...26 ...

Page 27: ...27 ...

Page 28: ...orld s leading developer of products in the field of electromechanical locking technology ASSA ABLOY is the global leader in door opening solutions dedicated to satisfying end user needs for security safety and convenience ISO 9001 ISO 14001 CERTIFIED ORGANISATION Some of the materials in this product such as electronic components require specialist recycling techniques Nimike Päiväys 09 2009 DOOR...