Menu Tree
Main Display
Space Temp [AV33] R
– Current space temperature at the User
Interface (or remote space temperature sensor if equipped).
Quick Access
Fan Command [MSV51] R/W
– This is accessed by pressing the “up
arrow” from the main screen and is used to turn the unit ON and OFF. The
unit will cycle on and o
ff
to maintain space temperature by supplying the
temperature of air defined in the CONFIG menu.
Set Points
Mode [MSV53] R/W
– This is the mode of operation. Select “Heat” or
“Vent” as desired (if the unit has cooling installed the choices will be “Heat/
Cool/Air”)
Occ Set Point [AV51] R/W
– Occupied Heat Set Point.
Unoc Set Point [AV52] R/W
– Unoccupied Heat Set Point (only
available if the unit has scheduling as an option).
Burner Reset [MSV54] R/W
– Burner reset command for use during
a burner lockout alarm. This is an “on/_on_” toggle selectable via the “up
arrow” button.
Status
Space Temp [AV33] R
– Current space temperature at the User
Interface (or remote space temperature sensor if equipped).
Outside Temp [AV34] R
– Current outside air temperature.
Discharge Temp [AV35] R
– Current discharge air temperature.
Heat Command [AV32] R
– Current command (0% - 100%) issued
to the burner for heat.
010622
When viewing menu tree options, the standard convention is:
Point Name
(as listed on the HMI)
[BACnet ID] R
or
R/W
(read only or
read/write).
Example:
Space Temp [AV33] R