Removable Plugs
Dimensions
1.78" W x 4.62" H x 4.81" D
45 mm W x 117 mm H x 122 mm D
Height includes connectors
Sink or Source
mA Output for
Each Channel
Output LoopTracker
LED for Each
Channel
Adjustable Output
Test Function for
Each Channel
Zero and Span for
Each Channel
Built-in Excitation
Voltage for Strain
Gauge Input
Custom I/O Ranges
Description
The APD 2015 DuoPak accepts one RTD input and one strain
gauge input and provides two optically isolated DC voltage or
current outputs that are linearly related to the inputs.
The input ranges and the output ranges for each channel are
independent and can be specified as required. This provides an
economical two channel solution in one device.
Typical applications include signal conversion, isolation, and
redundancy (i.e. to prevent failure of the entire loop if one
device fails), or a combination of these.
Each input signal is filtered, amplified, and then passed
through an opto-coupler to the output stages. Full 5-way
isolation (input 1, input 2, output 1, output 2, power) make
this module useful for ground loop elimination, common mode
signal rejection, and noise pickup reduction.
Output Sink/Source Versatility
Standard on the APD 2015 are 20 VDC loop excitation sup-
plies for each output channel. These power supplies can be
selectively wired for sinking or sourcing allowing use with any
combination of powered or unpowered milliamp I/O devices.
LoopTracker
API exclusive features include four LoopTracker LEDs (green
for each input, red for each output) that vary in intensity with
changes in the process input and output signals.
These provide a quick visual picture of your process loop at all
times and can greatly aid in saving time during initial startup
and troubleshooting.
Output Test
An API exclusive feature includes output test buttons for each
channel to provide a fixed output (independent of the input)
when held depressed.
Terminals are also provided to operate the test functions
remotely for each channel. This also allows use as a remote
manual override to provide a temporary fixed output if desired.
The test output level for each channel is potentiometer adjust-
able from 0 to 100% of the output span. The output test greatly
aids in saving time during initial startup and/or troubleshooting.
Universal
Power
Input LoopTracker
LED for Each
Channel
®
Two Channel Signal Converter/Isolator/Transmitter, Factory Ranged
APD 2015
Channel 1: RTD Temperature to DC
O
Two Independent Channels with Full Isolation
O
Zero and Span for Each Output
O
Input and Output LoopTracker
®
LEDs
O
Output Test/Manual Override for Each Channel
O
Built-In I/O Power Supplies
Q
Monitor Temperature and Weight or Pressure
Q
Convert/Isolate Dual Output Transmitters
Applications
Channel 1 RTD Input Range
Factory configured, please provide complete sensor specifica-
tions and temperature range. 100°F (55°C) minimum span.
RTD input:
Resistance at 0°C
Curve (385, 3916, 392 etc.)
Temperature range in °F or °C
RTD resistance: Typically 10
Ω
to 2000
Ω,
2 or 3 wire
Excitation current: Typically 10
Ω
: 10 mA, 100
Ω
: 2 mA,
1000
Ω
: 0.5 mA, 2000
Ω
: 0.2 mA
Leadwire comp.: < ±0.05% of span per 1
Ω
change in
leadwire resistance, 3 wire sensor
Channel 2 Bridge Input Range
Factory configured, please specify sensor mV/V and mV range
Sensor range:
0-1 mV to 0-2000 mV
Millivolt output range is determined by the sensitivity of the
sensor (mV/V) and the excitation voltage applied.
mV/V sensitivity X excitation voltage = total mV range
Input impedance:
1 M
Ω
minimum
Input com. mode rejection: 100 dB minimum
Channel 2 Excitation Voltage
Range:
4 to 10 VDC factory set, please specify
Adjustment:
±10% via front potentiometer
Maximum output: 10 VDC maximum at 30 mA
Stability:
±0.01% per °C
Designed for one 350
Ω
(or greater) sensor
LoopTracker
Variable brightness LEDs indicate I/O levels for each channel
Channel 1 and Channel 2 Output Ranges
Factory configured, please specify for each output channel
Voltage:
0-1 VDC to 0-10 VDC, 10 mA max
up to 20 VDC with M19, M29, M39
Bipolar voltage: ±1 VDC to ±10 VDC
Current:
0-1 mADC to 0-20 mADC, 4-20 mADC
20 V compliance, 1000
Ω
at 20 mA
Output Calibration
Multi-turn zero and span potentiometers for each output channel
±15% of span adjustment range typical
Output Characteristics
Linearity:
±0.1% of span
Temperature stability:
Better than 0.04% span/°C
Output ripple and noise:
Less than 10 mV
RMS
Isolation
Full 5-way, 1200 V
RMS
minimum
Response Time
70 milliseconds nominal
Output Loop Power Supplies
20 VDC nominal, regulated, 25 mADC for each output channel
May be selectively wired for sinking or sourcing mA output
Output Test
Front buttons set each output to test level when pressed
Each test level potentiometer adjustable 0-100% of span
Installation Environment
Mount vertically to a 35 mm DIN rail
For use in Pollution Degree 2 Environment
IP 40 housing, requires installation inside an enclosure
–10°C to +60°C operating ambient
Connectors
Eight 4-terminal removable connectors, 14 AWG max wire size
Power
85-265 VAC, 50/60 Hz or 60-300 VDC, 6 W maximum
D versions: 9-30 VDC or 10-32 VAC 50/60 Hz, 6 W maximum
Channel 2: Bridge/Strain Gauge/Load Cell to DC
Options—add to end of model number
R1
Channel 1 I/O reversal (i.e. 20-4 mA out)
R2
Channel 2 I/O reversal (i.e. 20-4 mA out)
R3
Channel 1 and channel 2 I/O reversal
M19
Channel 1 high voltage output >10 V up to 20 V
M29
Channel 2 high voltage output >10 V up to 20 V
M39
Channel 1 and channel 2 high voltage output
U
Conformal coating for moisture resistance
Accessory—order as separate line item
API BP4
Spare removable 4 terminal plug, black
How to Order
Models are factory ranged. See I/O ranges above left.
Ranges and options for each channel must be specified on order
Channel 1 input range
Channel 2 input range, excitation voltage
Channel 1 output range
Channel 2 output range
Model
Description
Power
APD 2015
DuoPak 2 channel
RTD-DC, Strain-DC
converter/isolator/
transmitter
85-265 VAC, 50/60 Hz or
60-300 VDC
APD 2015 D
9-30 VDC or 10-32 VAC
Options and Accessories
©
03-22
1220 American Way Libertyville, IL 60048
Phone:
800-942-0315
Fax: 800-949-7502
A
A
BSOLUTE
BSOLUTE
P
P
ROCESS
ROCESS
I
I
NSTRUMENTS
NSTRUMENTS
1 2 3 4
5 6 7 8
9 10 11 12
13 14 15 16
25 26 27 28
29 30 31 32
17 18 19 20
21 22 23 24
See Wiring
Diagrams on
Next Page
Free Factory
I/O Setup!
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
H H H H H
H H H H H H
Made in USA
File E145968
85-265 VAC, 60-300 VDC
model only
Quick Link