background image

Performance Data

 

GFMJ Series 12V Battery Constant Current Discharge (Amperes @ 20

 

Constant Current Discharge Data Sheet (20

)-------Amperes(A) 

Battery Type 

End Voltage 

(V/cell) 

Discharge Time 

5min  10min  15min  20min  30min  45min 

1 h 

1.5 h 

2 h 

3 h 

5 h 

10 h 

20 h 

24 h 

48 h  100 h  120 h  240 h 

6GFMJ-200 

1.60 

559 

407 

317 

266 

194 

152 

115.6  89.8 

68.8  52.40  35.00  20.00  10.80  9.24 

4.86 

2.50 

2.18 

1.16 

1.65 

530 

393 

311 

262 

192 

149 

113.4  88.6 

68.8  52.40  35.00  20.00  10.80  9.24 

4.86 

2.50 

2.18 

1.16 

1.70 

499 

372 

305 

256 

190 

145 

113.4  87.2 

68.8  52.40  35.00  20.00  10.80  9.24 

4.86 

2.50 

2.18 

1.16 

1.75 

462 

346 

295 

246 

184 

141 

111.4 

86 

68.8  52.40  35.00  20.00  10.80  9.24 

4.86 

2.50 

2.18 

1.16 

1.80 

395 

315 

276 

229 

174 

136 

110.0  83.6 

66.8  50.00  34.00  20.00  10.40  8.80 

4.86 

2.50 

2.18 

1.16 

 

GFMJ Series 2V Battery Constant Current Discharge (Amperes @ 20

 

Constant Current Discharge Data Sheet (20

)-------Amperes(A) 

Battery Type 

End Voltage 

(V/cell) 

Discharge Time 

5min  10min  15min  20min  30min  45min 

1 h 

1.5 h 

2 h 

3 h 

5 h 

10 h 

20 h 

24 h 

48 h  100 h  120 h  240 h 

GFMJ-200 

1.65 

340 

310 

288 

260 

202 

125 

75 

55 

38 

34.00  26.60  22.10  11.20  9.45 

4.86 

2.51 

2.18 

1.16 

1.70 

320 

295 

260 

227 

190 

123 

73.7 

54.4 

37.1  32.20  25.80  21.30  10.80  9.20 

4.86 

2.51 

2.18 

1.16 

1.75 

300 

279 

248 

219 

184 

121 

72.3 

53.6 

36.4  31.70  25.30  20.90  10.60  9.10 

4.86 

2.51 

2.18 

1.16 

1.80 

280 

265 

229 

202 

170 

112 

69.4 

51.2 

35 

30.50  24.30  20.00  10.20  9.02 

4.86 

2.51 

2.18 

1.16 

1.85 

240 

229 

209 

189 

159 

108 

65.3 

48.0 

32.9  28.60  22.80  18.90  9.80 

8.90 

4.86 

2.51 

2.18 

1.16 

GFMJ-300 

1.65 

510 

465 

432 

390 

303 

188 

112.5  82.5 

57 

51.00  39.90  33.75  16.95  14.22  7.29 

3.75 

3.27 

1.74 

1.70 

480 

443 

390 

341 

285 

185 

110.6  81.6  55.65  48.30  38.70  31.95  16.65  14.05  7.29 

3.75 

3.27 

1.74 

1.75 

450 

419 

372 

329 

276 

182  108.5  80.4 

54.6  47.55  37.95  31.35  16.50  13.90  7.29 

3.75 

3.27 

1.74 

1.80 

420 

398 

344 

303 

255 

168  104.1  76.8 

52.5  45.75  36.45  30.00  16.20  13.72  7.29 

3.75 

3.27 

1.74 

1.85 

360 

344 

314 

284 

239 

162 

98.0 

72.0 

49.4  42.90  34.20  28.35  15.30  13.20  7.29 

3.75 

3.27 

1.74 

GFMJ-400 

1.65 

680 

620 

576 

520 

404 

250 

150 

110 

76 

68.00  53.20  45.00  22.60  19.02  9.72 

5.00 

4.36 

2.32 

1.70 

640 

590 

520 

454 

380 

246  147.4  108.8  74.2  64.40  51.60  42.60  22.20  18.68  9.72 

5.00 

4.36 

2.32 

1.75 

600 

558 

496 

438 

368 

242  144.6  107.2  72.8  63.40  50.60  41.80  22.00  18.58  9.72 

5.00 

4.36 

2.32 

1.80 

560 

530 

458 

404 

340 

224  138.8  102.4 

70 

61.00  48.60  40.00  21.60  18.43  9.72 

5.00 

4.36 

2.32 

1.85 

480 

458 

418 

378 

318 

216  130.6  96.0 

65.8  57.20  45.60  37.80  20.40  17.60  9.72 

5.00 

4.36 

2.32 

GFMJ-500 

1.65 

850 

775 

720 

650 

505 

313  187.5  137.5 

95 

85.00  66.50  56.25  28.25  23.75  12.15  6.25 

5.45 

2.90 

1.70 

800 

738 

650 

568 

475 

308  184.3  136  92.75  80.50  64.50  53.25  27.75  23.30  12.15  6.25 

5.45 

2.90 

1.75 

750 

698 

620 

548 

460 

303  180.8  134 

91 

79.25  63.25  52.25  27.50  23.10  12.15  6.25 

5.45 

2.90 

1.80 

700 

663 

573 

505 

425 

280  173.5  128 

87.5  76.25  60.75  50.00  27.00  23.10  12.15  6.25 

5.45 

2.90 

1.85 

600 

573 

523 

473 

398 

270  163.3  120.0  82.3  71.50  57.00  47.25  25.50  22.00  12.15  6.25 

5.45 

2.90 

GFMJ-600 

1.65 

1020 

930 

864 

780 

606 

375 

225 

165 

114  102.00  79.80  67.50  33.90  27.72  14.58  7.50 

6.54 

3.48 

1.70 

960 

885 

780 

681 

570 

369  221.1  163.2  111.3  96.60  77.40  63.90  33.30  27.72  14.58  7.50 

6.54 

3.48 

1.75 

900 

837 

744 

657 

552 

363  216.9  160.8  109.2  95.10  75.90  62.70  33.00  27.72  14.58  7.50 

6.54 

3.48 

1.80 

840 

795 

687 

606 

510 

336  208.2  153.6  105  91.50  72.90  60.00  32.40  27.72  14.58  7.50 

6.54 

3.48 

1.85 

720 

687 

627 

567 

477 

324  195.9  144.0  98.7  85.80  68.40  56.70  30.60  26.40  14.58  7.50 

6.54 

3.48 

 
 

 

 

07

 

Summary of Contents for 6GFMJ-100

Page 1: ......

Page 2: ...res 01 3 Applications 02 4 Standards 02 5 Certification 02 6 Battery construction 02 7 General Specifications 04 8 Technology 05 9 Performance Data 06 10 Operating instruction and Guidelines 12 11 Installation and Commissioning and Maintenance 14 ...

Page 3: ...d long cyclic life Patented relief valve Multi fold vent system comprised of proprietary gel specialized low pressure safety valve with acid filtering and flash arrester minimizes bulging and prevents flash back explosion from external ignition source Long service life The grid is made of lead calcium tin alloy which has effect against corrosion effect and provide good gas recombination technology...

Page 4: ...nd vibration resistant prevents leakage and container deformation Applications Telecommunication base station exchange station Dedicated telecommunication station for power system military station Data transmission and TV signal transmission EPS UPS Wind solar energy and wind pv hybrid power system Certification CE UL GOST Standards IEC60896 21 22 2004 IEC61427 2005 DIN43539 T5 1984 YD T1360 2005 ...

Page 5: ...GFMJ 200 and GFMJ 300 GFMJ 400 500 600 GFMJ 800 and GFMJ 1000 GFMJ 1200 GFMJ 1500 and GFMJ 2000 03 ...

Page 6: ...J 150 12 150 188 513 232 218 228 63 8 560 1600 3 65 M8 Φ16 D 6GFMJ 200 12 200 250 513 296 5 218 228 82 8 660 1850 3 20 M8 Φ16 D GFMJ 200 2 200 250 171 107 334 344 14 8 800 1900 0 68 M8 Φ18 F GFMJ 300 2 300 375 171 151 334 344 21 3 1000 2000 0 54 M8 Φ18 F GFMJ 400 2 400 500 211 175 334 344 30 1500 2800 0 45 M8 Φ18 H GFMJ 500 2 500 625 243 174 334 344 35 5 2000 3200 0 39 M8 Φ18 H GFMJ 600 2 600 750 ...

Page 7: ...lcium alloy which inhibit the hydrogen evolution The batteries apply special gel electrolyte technology and the gel is with three dimensional net porous structures and also with some tiny cracks as gas passage The oxygen from positive electrode get to negative through the special gel and rapidly react with the spongy lead existing on the negative electrode and produce water This process is called ...

Page 8: ...5 49 1 38 2 29 2 22 30 14 90 8 50 4 59 3 93 2 07 1 06 0 93 0 49 1 65 225 167 132 111 82 64 48 2 37 7 29 2 22 30 14 90 8 50 4 59 3 93 2 07 1 06 0 93 0 49 1 70 212 158 130 109 81 62 48 2 37 1 29 2 22 30 14 90 8 50 4 59 3 93 2 07 1 06 0 93 0 49 1 75 197 147 125 104 78 60 47 3 36 6 29 2 22 30 14 90 8 50 4 59 3 93 2 07 1 06 0 93 0 49 1 80 168 134 117 97 74 58 46 8 35 5 28 4 21 30 14 50 8 50 4 42 3 74 2...

Page 9: ...6 81 6 55 65 48 30 38 70 31 95 16 65 14 05 7 29 3 75 3 27 1 74 1 75 450 419 372 329 276 182 108 5 80 4 54 6 47 55 37 95 31 35 16 50 13 90 7 29 3 75 3 27 1 74 1 80 420 398 344 303 255 168 104 1 76 8 52 5 45 75 36 45 30 00 16 20 13 72 7 29 3 75 3 27 1 74 1 85 360 344 314 284 239 162 98 0 72 0 49 4 42 90 34 20 28 35 15 30 13 20 7 29 3 75 3 27 1 74 GFMJ 400 1 65 680 620 576 520 404 250 150 110 76 68 0...

Page 10: ... 204 00 159 60 135 00 67 80 57 50 29 16 15 00 13 08 6 96 1 70 1920 1770 1560 1362 1140 738 442 2 326 4 222 6 193 20 154 80 127 80 66 60 57 30 29 16 15 00 13 08 6 96 1 75 1800 1674 1488 1314 1104 726 433 8 321 6 218 4 190 20 151 80 125 40 66 00 57 00 29 16 15 00 13 08 6 96 1 80 1680 1590 1374 1212 1020 672 416 4 307 2 210 183 00 145 80 120 00 64 80 56 80 29 16 15 00 13 08 6 96 1 85 1440 1374 1254 1...

Page 11: ... 5 95 3 16 1 63 1 43 0 76 1 75 251 203 173 147 113 85 67 52 5 42 3 30 60 20 90 12 10 6 60 5 95 3 16 1 63 1 43 0 76 1 80 234 185 165 138 108 82 66 0 51 3 41 2 29 80 19 80 11 80 6 40 5 72 3 16 1 63 1 43 0 76 6GFMJ 85 1 60 419 314 246 207 155 117 90 8 70 6 55 3 40 00 27 40 16 20 8 70 7 78 4 13 2 13 1 87 0 99 1 65 390 302 241 204 154 116 89 2 70 55 3 40 00 27 40 16 00 8 70 7 78 4 13 2 13 1 87 0 99 1 7...

Page 12: ...39 104 71 48 60 38 50 31 90 18 30 16 70 9 72 5 00 4 40 2 34 1 75 547 515 462 410 346 229 138 103 70 46 90 37 20 30 70 18 30 16 50 9 72 5 00 4 40 2 34 1 80 523 498 434 383 325 214 135 99 68 45 20 35 80 30 00 18 30 16 10 9 72 5 00 4 40 2 34 1 85 458 439 402 366 309 211 128 0 94 0 65 0 42 90 34 10 28 30 17 60 15 30 9 72 5 00 4 40 2 34 GFMJ 300 1 65 891 827 777 707 554 348 210 156 108 75 15 60 00 49 5...

Page 13: ...170 1915 1625 1070 675 495 340 226 00 179 00 150 00 80 50 91 50 48 60 25 00 22 00 11 70 1 85 2290 2195 2010 1830 1545 1055 640 0 470 0 325 0 215 00 171 00 142 00 76 50 88 00 48 60 25 00 22 00 11 70 GFMJ 1200 1 65 3564 3306 3108 2826 2214 1392 840 624 432 300 60 240 00 198 00 101 40 100 20 58 32 30 00 26 40 14 04 1 70 3414 3204 2850 2508 2106 1380 834 624 426 291 60 231 00 191 40 100 20 99 30 58 32...

Page 14: ...22 30 2 21 35 2 19 3 2 The batteries need an equalization charge or supplemental charge in the following conditions Supplemental charge battery after the installation of battery system and before the operation The batteries are on shelf for six months Floating operation for a long time or not discharge 40 C20 plus the batteries need an equalization charge regularly and the equalizing charge cycle ...

Page 15: ...to constant voltage h Constant voltage V cell Charging time h 20 0 1C10 1 6 2 35 8 0 15C10 1 2 2 35 6 50 0 1C10 4 3 2 35 14 0 15C10 3 3 2 35 12 80 0 1C10 6 8 2 35 16 0 15C10 5 5 2 35 14 100 0 1C10 8 7 2 35 18 0 15C10 6 8 2 35 16 6 Storage GEL batteries should be stored in a dry clean and ventilated location Since the batteries are fully charged the recommended storage time is as follows 6 months a...

Page 16: ...ord the ambient temperature of the battery room battery container and terminals Check container lid and terminal surface defects and temperature of each battery Measure and record the total voltage and floating current of the battery system Correct problems once found Quarterly Maintenance Repeat every item of monthly inspection Measure and record floating voltage of every on line battery Annually...

Page 17: ...ith Master distributors and Country managers who apply ABT commercial strategy and through Global Key Account in Advanced Battery Technology BV Add New Yorkstraat 14 1175 RD Lijnden Amsterdam Netherland Website www abtbatt com Email sales abtbatt com Version 201503 Copyright 2015 Advanced Battery Technology BV All rights reserved ...

Reviews: