Earthing/Grounding 
The HVJB unit is provided with an internal and external earthing/grounding facility. This must be 
connected to the appropriate earth bonding circuit before electrical power is connected to the 
contents of the enclosure. Any earth/ground conductor brought into the enclosure must be 
terminated onto the enclosure internal earth/ground stud.  

Operation 
1.  The lid must be secured using all the lid screws provided in order to maintain the IP rating. 

2.  No attempt must be made to remove the enclosure lid whilst electrical power is connected to 

the contents of the enclosure. 

3.  The earthing/grounding facility must be connected to the earth bonding circuit at all times when 

electrical power is connected to the enclosure. 

Maintenance  
Routine maintenance is a requirement of IEC 60079-17:1996 and is also likely to be a requirement 
of local Health and Safety legislation.  The laws of the applicable country must be considered and 
maintenance checks carried out accordingly. 

Additional checks that are advisable to ensure the efficiency of ABTECH ‘S’ range enclosures on 
which the HVJB is based are:- 

Activity Frequency 

Check that the lid seal is not damaged and is in place 

Each time the 
enclosure is opened 

Check that all lid fixing screws are in place and secured 

Each time the 
enclosure is opened 

Check that all gland plate fixing screws are in place and secured 

Each time the 
enclosure is opened 

Check that the mounting bolts are tight and free of corrosion 

Annually 

Check the security of all cable glands 

Annually 

Check the enclosure for damage 

Annually 

 
Chemical attack 
The ABTECH HVJB is manufactured from 316 stainless steel. The following additional material are 
also used :- 

Neoprene or silicone rubber, 
Copper, 
Brass, 
Cast epoxy resin. 

The user should give consideration to any aggressive and corrosive substances that may be 
present in the environment in which these enclosures are to be used to determine the suitability of 
these materials to withstand those substances. 

Static hazard 
The HVJB does not present a hazard from static electricity. 

Vibration 
The HVJB is designed for use in areas subject to normal industrial levels of vibration. They are not 
designed for use in areas subject to intentional or extreme conditions of vibration. 