Air Handlers
5
NOTES:
①
. Based upon W/nominal tonnage, dry coil and filter should be installed.
②
. Use 0.96 as approximate SCFM correction factor for wet coil.
2.6 Dip switch configuration
Set the indoor fan speed through the eight dip switches of the indoor main control
board. The higher level, the higher speed of the indoor unit fan. Operation Instruction is
below:
Dip switch settings must be completed before power on the unit.
Model
Level
Heat (SA2)
Cool (SA1)
AUD24AH2/A1-D(U)
Level 1
1
0
0
0
0
0
0
0
Level 2
1
0
0
1
0
0
0
0
Level 3
1
0
1
0
0
0
0
0
Level 4-Default
1
0
1
1
0
0
0
0
Level 5
1
1
0
0
0
0
0
0
Level 6
1
1
0
1
0
0
0
0
Level 7
1
1
1
0
0
0
0
0
Level 8
1
1
1
1
0
0
0
0
AUD36AH2/A1-D(U)
Level 1
0
0
0
0
0
0
0
0
Level 2
0
0
0
1
0
0
0
0
Level 3
0
0
1
0
0
0
0
0
Level 4-Default
0
0
1
1
0
0
0
0
Level 5
0
1
0
0
0
0
0
0
Level 6
0
1
0
1
0
0
0
0
Level 7
0
1
1
0
0
0
0
0
Level 8
0
1
1
1
0
0
0
0
AUD48AH2/A1-D(U)
Level 1
1
0
0
0
0
0
0
0
Level 2
1
0
0
1
0
0
0
0
Level 3
1
0
1
0
0
0
0
0
Level 4-Default
1
0
1
1
0
0
0
0
Level 5
1
1
0
0
0
0
0
0
Level 6
1
1
0
1
0
0
0
0
Level 7
1
1
1
0
0
0
0
0
Level 8
1
1
1
1
0
0
0
0
Summary of Contents for AUD24AH2/A1-D
Page 4: ......