ƳƷ
(3)High temperature and overload protection diagnosis (AP1 hereinafter refers to the control board of the out-
door unit)
Mainly detect:
z
Is outdoor ambient temperature in normal range?
z
Are the outdoor and indoor fans operating normally?
z
Is the heat dissipation environment inside and outside the unit is good?
End
Y
Y
N
Y
N
N
Y
N
Overheat and high
temperature protection
Is outdoor ambient temperature higher than 53?
20 minutes after the complete
unit is powered off.
Is heat dissipation of the indoor unit
and outdoor unit abnormal?
Normal protection, please operate
it after the outdoor ambient temp-
erature is normalized.
Improve the heat
dissipation environ-
ment of the unit
Does the outdoor fan work normally?
1. Check if the fan terminal OFAN
is connected correctly
2.
拔掉风机针座,用欧姆
表测量风机端任意两个端子间电阻,
阻值小于
1KOhm
Replace the
control panel
AP1
Replace the
outdoor fan