SCL/SCM CONTROL WIRING DIAGRAMS
11.1 SCL/SCM Terminal Strip
Shown below is the control terminal strip, along with a brief description of the function of
each terminal . The following wiring diagram examples provide a quick reference to wire
the drive for the most common configurations .
Maintained
RUN/STOP
Contact
1
2
25
13A
13E
13B
RUN
5
6
11
16
17
SIGNAL COMMON
0-10V DC INPUT
TB-13A FUNCTION SELECT
TB-13B FUNCTION SELECT
TB-13E FUNCTION SELECT
4-20mA INPUT
FORM A RELAY
-
+
+
SPEED POT POWER SUPPLY
DIGITAL INPUT REFERENCE
SCL/SCM Terminal Strip
NOTE
•
The function of terminals TB-13A, 13B, 13E and the Form A relay at terminals
16 and 17 are dependent on the programming of certain parameters .
Refer to Section 15, DESCRIPTION OF PARAMETERS .
•
The digital inputs (terminals 1, 13A, 13B, and 13E) are active-high . They can
be activated using terminal 11 (which is +12 VDC) as shown in the following
diagrams, or by using an external voltage source with a range of +12 VDC to
+28 VDC (+ 10%) .
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com