SM01P
44
P50
FAULT HISTORY
The FAULT HISTORY stores the last eight faults that tripped the drive . Refer to Section
16, TROUBLESHOOTING for a list of the faults and possible causes .
Use the
and
buttons to scroll through the fault entries . The faults are stored from
newest to oldest, with the first fault shown being the most recent .
The display will read “_ _” if the FAULT HISTORY does not contain any fault messages .
P51
SOFTWARE VERSION
Parameter P51 displays the software version number for the control board software . This
information is useful when contacting the factory for programming or troubleshooting
assistance .
The software version is displayed in two parts which alternate . The first part is the software
version, and the second part is the revision number . For example, if the display flashes
"94" and "02", this indicates that the drive contains the second revision of version 94
software .
P52
DC BUS VOLTAGE
P52 displays the DC bus voltage in percent of nominal . Nominal DC bus voltage is
determined by multiplying the drive’s nameplate input voltage rating by 1 .4 .
P53
MOTOR VOLTAGE
P53 displays the output voltage in percent of the drive’s nameplate output voltage
rating .
P54
MOTOR LOAD
P54 displays the motor load in percent of the drive’s output current rating .
P55
0-10 VDC INPUT
Parameter P55 displays the level of the 0-10 VDC input signal at TB-5 . A reading of 100%
indicates a 10 VDC input at TB-5 .
P56
4-20 mA INPUT
Parameter P56 displays the level of the 4-20 mA input signal at TB-25 . A reading of
20% indicates a 4 mA input at TB-25, and a reading of 100% indicates a 20 mA input at
TB-25 .
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com