28
Smoke exhaust / combustion air intake
The X series warm air heaters are suitable for the following flue gas exhaust / combustion air intake
configurations:
• from model 50 to model 300 and variants:
• B23;
• C13, C33, C53, (sealed type systems)
• from model 425 to model 600 and variants:
• B23
We invite you to inform yourself about the regulations in force at national and local level on the subject to make sure
that the outlet / intake system chosen is in compliance with the law.
Respect the installation diagrams contained in this manual.
The sum of the maximum pressure drop between the flue gas discharge and combustion air intake pipes (where
present), terminals included, must not exceed 50 Pa.
For more information regarding duct joints, please contact the manufacturer or your supplier directly.
Below is the table of the pressure drops of the elements supplied by the manufacturer that make up the flue gas exhaust
/ combustion air intake system.
These pipes and elements (POCED) are made of smooth single-walled AISI 316 stainless steel, suitable for outdoor
installation, certified according to EN 1856-1: 2009. On request we can also supply multi-wall elements.
The tightness of the junction between the elements is ensured by silicone gaskets and clamps.
In the case of warm air heaters installed outdoors (XE, XEO, XP series), the vertical terminal must be of the weatherproof
type, to protect against rain, snow, leaves.
The length of the smoke outlet must be contained between 2 and 8 meters.
Below is an example of assembly of the elements