32
Operating conditions:
(1) Cooling: Outdoor air temperature 35°C; inlet/outlet temperature 12/7°C.
(2)
Cooling: Outdoor air temperature 35°C; inlet/outlet temperature 23/18°C.
(3)
Heating: Outdoor air temperature 7°C DB 6°C WB; inlet/outlet temperature 30/35°C.
(4) Heating: Outdoor air temperature 7°C DB 6°C WB; inlet/outlet temperature 40/45°C.
(5) Cooling: water temperature inlet/outlet 12/7°C.
(6) Heating: normal climatic condition; Tbiv=-7°C; eater temperature inlet/outlet 30/35°C.
(7) The data are only indicative and subject to change. For the correct data, refer to the technical label sticked on the unit.
(8) Calculated in the case of the plant water temperature decrease with 15°C for 6 minutes of defrosting operation.
(9) Power sound: condition (3); the value is determined based on the measurements taken in accordance with the UNI EN ISO 9614-2, in compliance with the
requirements of Eurovent certification. The data with installed accessories SL or SSL are also reported.
(10) The sound pressure value is calculated from the sound power level in accordance with ISO 3744: 2010, referred to 10 m away from the unit. The values with
installed accessories SL or SSL are also reported.
(11) Packing’s height includes the pallet.
(*) The available pressure head and characteristics of the pump refer to “CI1” kit for all sizes except 0270 for which the data are expressed for “CI6” kit
N.B. The performance data are indicative and could be subject to change. In addition, the performances declared in apex (1), (2), (3) and (4) refer to the
instantaneous power according to EN 14511. The declared data stated in the apex (6) is determined according to the UNI EN 14825.
WARNING: The minimum temperature allowed for storing the unit is 5°C.
14
ELECTRIC DATA OF THE UNIT AND AUXILIARIES
Power supply of the unit
V/~/Hz
400/3/50
Remote control circuit
V/~/Hz 12/1/50
Control board circuit
V/~/Hz
12/1/50
Fans power supply
V/~/Hz 230/1/50
Note: Electric data may change for updating. It is therefore necessary to refer always to the technical data label sticked on right-
side panel of the unit.
15
AVAILABLE HEAD PRESSURE OF THE UNIT WITH INTEGRATED CIRCULATOR
We reporte below the Head pressure-Water flow characteristic curves without consideration of head losses of the hydronic kit
(which is consisting of the components describe in the Paragraph 5.10) at the maximum speed of the circulator. The optimal
operating point is indicated on each curve under the specified conditions indicated at apex (1) p. 27. The plant system must be
designed so as to ensure the nominal water flow rate corresponding to the operating points indicated below.
For nominal points of LT version, please refer to water flow rates that are reported in the table on Paragraph 13.2.
Dimensions and
weights
Dimensions (L×H×W)
mm
1198x1673x1198
1198x1673x1198
1198x1745x1198
Dimensions SSL version (L×H×W)
mm
1198x1915x1198
1198x1915x1198
1198x1920x1198
Max packing dimensions (LxHxW) (11)
mm
1200x1765x1200
1200x1765x1200
1200x1890x1200
Max packing dimensions SSL version
(LxHxW) (11)
mm
1200x2045x1200
1200x2045x1200
1200x2050x1200
Shipping weight
kg
385
391
444
460
460
468
Operating weight
kg
373
389
432
450
442
456